Installer Setting - How To Enter Installer Setting Mode - LG ABNW54LM3S1 Installation Manual

Table of Contents

Advertisement

Installer Setting - How to enter installer setting mode

CAUTION
!
Installer setting mode is to set the detail function of the remote controller.
If the installer setting mode is not set correctly, it can cause problems to the product, user
injury or property damage. This must be set by an certificated installer, and any installation
or change that is carried out by a non-certificated person should be responsible for the
results. In this case, free service cannot be provided.
<Installer Setting Code Table>
General air-conditioner product
No.
Function
1
Test Run
2
Address Setting
3
E.S.P. Value
4
Thermistor
5
Ceiling Height
6
Static Pressure
7
Master Setting
Celsius
8
Fahrenheit Switching
Static Pressure
9
Step
* Some contents may not be displayed depending on the product function
If you want to set installer setting mode,
1
Press the Temperature up button and the oper
mode button same time for five seconds.
When you enter the setting mode
2
Initially. Function code is displayed
on the LCD screen.
Code
01
01:Set
02
00~FF : Address
<ESP Step>
01:VeryLow
02:Low
03
03:Med
04:High
05:Very High
01:Remo
04
02:Indoor
03:2TH
01:Med
02:Low
05
03:High
04:Very High
01:V-H
02:F-H
06
03:V-L
04:F-L
00:Slave
07
01:Master
00:Celsius
12
01:Fahrenheit
00: use static pressure (code 06) set value
32
01~ 11: static pressure step (code 32) set value
INSTALLATION INSTRUCTION
Function Code
Value
Value
<ESP Value><Example>
0 ~ 255
Function Code
ESP step
(Optimized only for U.S.A)
19
ESP value

Advertisement

Table of Contents
loading

This manual is also suitable for:

Abnw36gm2s1Abnw24gm1s1Abnw48lm3s1

Table of Contents