8. Control Terminal Functions
8.1. Digital Input Configuration Parameter P1-13
Local
P1-13
(Hand)
Digital Input 1
Control
(Terminal 2)
*(2)
Function
0
N/A
All functions User defined in Menu 9 or configured through PLC function in OptiTools studio software suite.
O: Stop
1
*(3)
C: Run/Enable
O: No Function
2
C: Momentary Start
Analog
Input 2
O: Stop
3
C: Run/Enable
O: Stop
4
C: Run/Enable
O: Stop
5
C: Run/Enable
Preset
O: No Function
6
Speeds
C: Momentary Start
O: Stop
7
C: Run/Enable
O: Stop
8
C: Run/Enable
O: Stop
9
*(3)
C: Run/Enable
O: Stop
10
*(3)
C: Run/Enable
Keypad
Speed
O: No Function
11
Reference
C: Momentary Start
O: Stop
12
C: Run Fwd
O: Stop
13
C: Run Fwd
O: Stop
14
C: Run
Notes
*
(1)
: Logic shown is as per the default setting. Fire mode logic can be configured through parameter P8-09.
*
(2)
: Default setting for P1-13 = 1.
*
(3)
: When the drive is in PID control (P1-12 = 3) and digital preset reference is selected (P3-05 = 0) then P1-13 can be set to 1, 9, or
10 to allow selection between two independent digital references using digital input 2. Digital preset reference 1 and 2 are set in
P3-06 and P3-15 respectively.
"Motor thermistor trip" connection is via analog input 2 and is configured by parameter P2-33 (Pt-th).
NOTE
www.invertekdrives.com
Digital
Digital Input 2
Input 3
(Terminal 3)
(Terminal 4)
O: Normal Operation
O: Remote Ctrl
C: Preset 1/
C: Local Ctrl
PI Set-point 2
O: Stop (Disable)
O: Remote Ctrl
C: Run Permit
C: Local Ctrl
O: Forward
O: Remote Ctrl
C: Reverse
C: Local Ctrl
O: Fire Mode
O: Remote Ctrl
*(1)
C: Normal Operation
C: Local Ctrl
*(1)
O: Preset Speed 1
O: Remote Ctrl
C: Preset Speed 2
C: Local Ctrl
O: Stop (Disable)
O: Remote Ctrl
C: Run Permit
C: Local Ctrl
O: Forward
O: Remote Ctrl
C: Reverse
C: Local Ctrl
O: Fire Mode *
O: Remote Ctrl
(1)
C: Normal Operation
*(1)
C: Local Ctrl
O: Normal Operation
O: Remote Ctrl
C: Preset 1/
C: Local Ctrl
PI Set-point 2
O: Normal Operation
O: Remote Ctrl
C: Preset 1/
C: Local Ctrl
PI Set-point 2
O: Stop (Disable)
O: Remote Ctrl
C: Run Permit
C: Local Ctrl
O: Forward
O: Remote Ctrl
C: Reverse
C: Local Ctrl
O: Fire Mode
O: Remote Ctrl
*(1)
C: Normal Operation
* (1)
C: Local Ctrl
Digital
input 3
Off
On
O: Forward
Off
C: Reverse
On
Off
On
Off
On
Analog
Analog
Input 1
Input 2
(Terminal
(Terminal 10)
6)
Analog In 1
Analog In 2
Analog In 1
Analog In 2
Analog In 1
Analog In 2
Analog In 1
Analog In 2
O: Ext Trip
Analog In 1
C: Normal
Operation
O: Preset 1
Analog In 1
C: Preset 2l
O: Preset 1
Analog In 1
C: Preset 2
O: Preset 1
Analog In 1
C: Preset 2
Analog In 1
Analog In 2
O: Ext Trip
Analog In 1
C: Normal
Operation
Analog In 1
Analog In 2
Analog In 1
Analog In 2
Analog In 1
Analog In 2
Analog
Analog
Preset
input 1
input 2
Speed
Off
Off
Preset Speed 1
Off
Off
Preset Speed 2
On
Off
Preset Speed 3
On
Off
Preset Speed 4
Off
On
Preset Speed 5
Off
On
Preset Speed 6
On
On
Preset Speed 7
On
On
Preset Speed 8
Version 3.06 | Optidrive Eco User Guide | 39
Notes
When Input 3
is Closed:
Speed
Reference =
Analog Input 2
Start Command
= Input 1
In PI Mode,
Analog Input 1
must be used
for feedback
When Input 3
is Closed:
Speed
Reference =
Preset Speed
1 / 2
Start Command
= Input 1
When Input 3
is Closed:
Speed
Reference =
Keypad
Start Command
= Determined
by P2-37
8