PERFORMANCE DATA COOL operation a
MUZ-HJ60VA
CAPACITY: 6.1 kW
INDOOR
INDOOR
DB (°C)
WB (°C)
Q
SHC
21
18
5.98
3.83
21
20
6.28
3.27
22
18
5.98
4.07
22
20
6.28
3.52
22
22
6.65
2.93
23
18
5.98
4.30
23
20
6.28
3.77
23
22
6.65
3.19
24
18
5.98
4.54
24
20
6.28
4.02
24
22
6.65
3.46
24
24
7.01
2.81
25
18
5.98
4.78
25
20
6.28
4.27
25
22
6.65
3.72
25
24
7.01
3.09
26
18
5.98
5.02
26
20
6.28
4.52
26
22
6.65
3.99
26
24
7.01
3.37
26
26
7.38
2.66
27
18
5.98
5.26
27
20
6.28
4.78
27
22
6.65
4.26
27
24
7.01
3.65
27
26
7.38
2.95
28
18
5.98
5.50
28
20
6.28
5.03
28
22
6.65
4.52
28
24
7.01
3.93
28
26
7.38
3.25
29
18
5.98
5.74
29
20
6.28
5.28
29
22
6.65
4.79
29
24
7.01
4.21
29
26
7.38
3.54
30
18
5.98
5.98
30
20
6.28
5.53
30
22
6.65
5.05
30
24
7.01
4.49
30
26
7.38
3.84
31
18
5.98
5.98
31
20
6.28
5.78
31
22
6.65
5.32
31
24
7.01
4.77
31
26
7.38
4.13
32
18
5.98
5.98
32
20
6.28
6.03
32
22
6.65
5.59
32
24
7.01
5.05
32
26
7.38
4.43
NOTE
Q : Total capacity (kW)
SHC : Sensible heat capacity (kW)
OBH648F
t Rated frequency
SHF: 0.82
INPUT: 1900 W
OUTDOOR DB (°C)
35
SHF
INPUT
Q
0.64
1862
5.49
0.52
1938
5.86
0.68
1862
5.49
0.56
1938
5.86
0.44
2014
6.22
0.72
1862
5.49
0.60
1938
5.86
0.48
2014
6.22
0.76
1862
5.49
0.64
1938
5.86
0.52
2014
6.22
0.40
2090
6.59
0.80
1862
5.49
0.68
1938
5.86
0.56
2014
6.22
0.44
2090
6.59
0.84
1862
5.49
0.72
1938
5.86
0.60
2014
6.22
0.48
2090
6.59
0.36
2166
6.95
0.88
1862
5.49
0.76
1938
5.86
0.64
2014
6.22
0.52
2090
6.59
0.40
2166
6.95
0.92
1862
5.49
0.80
1938
5.86
0.68
2014
6.22
0.56
2090
6.59
0.44
2166
6.95
0.96
1862
5.49
0.84
1938
5.86
0.72
2014
6.22
0.60
2090
6.59
0.48
2166
6.95
1.00
1862
5.49
0.88
1938
5.86
0.76
2014
6.22
0.64
2090
6.59
0.52
2166
6.95
1.00
1862
5.49
0.92
1938
5.86
0.80
2014
6.22
0.68
2090
6.59
0.56
2166
6.95
1.00
1862
5.49
0.96
1938
5.86
0.84
2014
6.22
0.72
2090
6.59
0.60
2166
6.95
SHF : Sensible heat factor
INPUT : Total power input (W)
40
SHC
SHF
INPUT
Q
3.51
0.64
1976
5.06
3.05
0.52
2033
5.43
3.73
0.68
1976
5.06
3.28
0.56
2033
5.43
2.74
0.44
2128
5.79
3.95
0.72
1976
5.06
3.51
0.60
2033
5.43
2.99
0.48
2128
5.79
4.17
0.76
1976
5.06
3.75
0.64
2033
5.43
3.24
0.52
2128
5.79
2.64
0.40
2185
6.22
4.39
0.80
1976
5.06
3.98
0.68
2033
5.43
3.48
0.56
2128
5.79
2.90
0.44
2185
6.22
4.61
0.84
1976
5.06
4.22
0.72
2033
5.43
3.73
0.60
2128
5.79
3.16
0.48
2185
6.22
2.50
0.36
2261
6.53
4.83
0.88
1976
5.06
4.45
0.76
2033
5.43
3.98
0.64
2128
5.79
3.43
0.52
2185
6.22
2.78
0.40
2261
6.53
5.05
0.92
1976
5.06
4.68
0.80
2033
5.43
4.23
0.68
2128
5.79
3.69
0.56
2185
6.22
3.06
0.44
2261
6.53
5.27
0.96
1976
5.06
4.92
0.84
2033
5.43
4.48
0.72
2128
5.79
3.95
0.60
2185
6.22
3.34
0.48
2261
6.53
5.49
1.00
1976
5.06
5.15
0.88
2033
5.43
4.73
0.76
2128
5.79
4.22
0.64
2185
6.22
3.62
0.52
2261
6.53
5.49
1.00
1976
5.06
5.39
0.92
2033
5.43
4.98
0.80
2128
5.79
4.48
0.68
2185
6.22
3.89
0.56
2261
6.53
5.49
1.00
1976
5.06
5.62
0.96
2033
5.43
5.23
0.84
2128
5.79
4.74
0.72
2185
6.22
4.17
0.60
2261
6.53
DB : Dry-bulb temperature
WB : Wet-bulb temperature
30
46
SHC
SHF
INPUT
3.24
0.64
2052
2.82
0.52
2147
3.44
0.68
2052
3.04
0.56
2147
2.55
0.44
2204
3.65
0.72
2052
3.26
0.60
2147
2.78
0.48
2204
3.85
0.76
2052
3.47
0.64
2147
3.01
0.52
2204
2.49
0.40
2280
4.05
0.8
2052
3.69
0.68
2147
3.25
0.56
2204
2.74
0.44
2280
4.25
0.84
2052
3.91
0.72
2147
3.48
0.60
2204
2.99
0.48
2280
2.35
0.36
2356
4.46
0.88
2052
4.13
0.76
2147
3.71
0.64
2204
3.24
0.52
2280
2.61
0.40
2356
4.66
0.92
2052
4.34
0.80
2147
3.94
0.68
2204
3.48
0.56
2280
2.87
0.44
2356
4.86
0.96
2052
4.56
0.84
2147
4.17
0.72
2204
3.73
0.60
2280
3.13
0.48
2356
5.06
1.00
2052
4.78
0.88
2147
4.40
0.76
2204
3.98
0.64
2280
3.39
0.52
2356
5.06
1.00
2052
4.99
0.92
2147
4.64
0.80
2204
4.23
0.68
2280
3.66
0.56
2356
5.06
1.00
2052
5.21
0.96
2147
4.87
0.84
2204
4.48
0.72
2280
3.92
0.60
2356