Technical Data; Burner Equipment - Riello G10 LC Installation, Use And Maintenance Instructions

Light oil burner
Table of Contents

Advertisement

TECHNICAL DATA

TYPE
Thermal power – output
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
For use on hot air generator the burner must be fitted with control box type 479SE or 539SE.
Burner with CE marking in conformity with EEC Directives: EMC 89/336/EEC - 2004/108/EC, Low
Voltage 73/23/EEC - 2006/95/EC, Machines 98/37/EEC and Efficiency 92/42/EEC.
The burner meets protection level of IP 40, EN 60529.
9
4
3
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Screws fixing air-damper
7 – Air damper
8 – Combustion head adjustment screw
9 – Lock-out lamp and reset button
10 – Flange with insulating gasket
464T1
54 – 120 kW
Light oil, viscosity 4 – 6 mm
Single phase, 230 V ± 10%
Run current 0.8 A – 2850 rpm – 298 rad/s
4 μF
Secondary 8 kV – 16 mA
Pressure 7 – 15 bar
0.170 kW
Fig. 1
7
6
6
10
D5396

BURNER EQUIPMENT

Quantity
2
1
4
1
1
GB
1
4.5 – 10 kg/h
2
/s at 20°C
~
50Hz
2
Description
Flexible oil pipes with nipples
Flange with insulating gasket
Screws and nuts for flange
to be fixed to boiler
Hinge
Screw and nuts for flange
8
1
5
20013654

Advertisement

Table of Contents
loading

This manual is also suitable for:

20013617

Table of Contents