Installation, use and maintenance instructions
Oil - kerosene burners
One stage operation
Parts Available from
www.sparesgiant.com
CODE
3746467
MODEL
G10
TYPE
464T52
2903442 (0) - 05/2008

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the G10 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Riello G10

  • Page 1 Installation, use and maintenance instructions Oil - kerosene burners One stage operation Parts Available from www.sparesgiant.com CODE MODEL TYPE 3746467 464T52 2903442 (0) - 05/2008...
  • Page 2: Technical Features

    TECHNICAL FEATURES Thermal power – output 54 – 120 kW – 4.5 – 10 kg/h Light oil, max. viscosity at 20 °C: 4 ÷ 6 mm /s (H = 11.86 kWh/kg) Fuel Kerosene, max. viscosity at 20 °C: 1.6 ÷ 6 mm /s (H = 11.97 kWh/kg) Electrical supply...
  • Page 3: Working Range

    WORKING RANGE Fuel output - kg/h Thermal power - kW D5669 DIMENSIONS Flange Burner Parts Available from www.sparesgiant.com D5670 3442...
  • Page 4: Installation

    INSTALLATION BOILER FIXING Put on the flange (1) the screw and two nuts, (see fig. 2). Widen, if necessary, the insulating gasket holes (5), (see fig. 3). Fix the flange (1) to the boiler door (4) using screws (2) and (if necessary) the nuts (3) interposing the insulating gasket (5), (see fig.
  • Page 5: Oil Lines

    OIL LINES PRIMING THE PUMP L meters Loosen the plug of the vacuum I. D. I.D. gauge (5, fig. 1) and wait until the meters 8 mm 10 mm fuel flows out. D5219 H = Difference of level. D5199 L = Max. length of the L meters suction line.
  • Page 6 BURNER ELECTRICAL WIRING 230V 50Hz WARNING Do not exchange the neutral with the phase. Switch with fuse 6A max. Regulating thermostat Limit thermostat with manual resetting Remote lock-out lamp (230V - 0.5A max.), if required Terminal block of control-box 530SE Parts Available from www.sparesgiant.com Valve...
  • Page 7: Combustion Adjustment

    COMBUSTION ADJUSTMENT FUEL LIGHT OIL In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and testing must be carried out observing the instruction manual of the boiler, including verification of the CO and CO concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.
  • Page 8 COMBUSTION ADJUSTMENT FUEL KEROSENE In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and testing must be carried out observing the instruction manual of the boiler, including verification of the CO and CO concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.
  • Page 9: Air Damper Adjustment

    Combustion head settings indicated in the schedule are valid for most cases. The setting of the fan output according to the installation should normally be done only through the air damper. Should one subsequently want to retouch also the setting of the combustion head, with the burner running, operate on the rod (1) with a 6 mm spanner (2) as follows: TURN TO THE RIGHT: (sign In order to increase the volume of air entering the combustion chamber and thus diminishing its...
  • Page 10: Electrode Setting

    It is important to take account of the fact that the air output of the fan differs according to whether the PANEL burner has its metal cover fitted or not. Therefore we recommended to proceed as follows: – adjust the air damper as indicated in the schedule (4); –...
  • Page 11 ONLY FOR LIGHT OIL ADJUSTMENTS, TO AVOID FLAME - DETACHMENT, AT BURNER - IGNITION This inconvenience can occur, when the temperature of the light-oil decreases below + 5 °C. 1) CORRECT POSITIONING OF THE ELECTRODES MOVE THE ELECTRODE HOLDER BACKWARDS TO THE END 4 ±...
  • Page 12 Parts Available from www.sparesgiant.com RIELLO S.p.A. I-37045 Legnago (VR) Tel.: +39.0442.630111 http:// www.rielloburners.com Subject to modifications...