Installation, use and maintenance instructions 安装 , 使用以及维护说明书 Light oil burner 轻油燃烧器 One stage operation 一段火运行 CODE - 编码 MODEL - 型号 TYPE - 类型 20013617 G10 LC 464T1 20013654 (2) - 05/2009...
Page 2
INFORMATION ABOUT THE INSTRUCTION MANUAL INTRODUCTION The instruction manual supplied with the burner: is an integral and essential part of the product and must not be sepa- rated from it; it must therefore be kept carefully for any necessary consultation and must accompany the burner even if it is transferred to another owner or user, or to another system.
TECHNICAL DATA TYPE 464T1 Thermal power – output 54 – 120 kW – 4.5 – 10 kg/h Fuel Light oil, viscosity 4 – 6 mm /s at 20°C Electrical supply Single phase, 230 V ± 10% 50Hz Motor Run current 0.8 A – 2850 rpm – 298 rad/s 4 μF Capacitor Ignition transformer...
WORKING FIELD (as EN 267) Fuel output - kg/h Thermal power - kW D5669 OVERALL DIMENSIONS Flange Burner D5670 BOILER FIXING BURNER FIXING AND It is necessary that the insulating gasket HINGE ASSEMBLY (9, fig. 1) is placed between the boiler door and the burner flange.
HYDRAULIC SYSTEMS Warning: before starting the burner make sure that the return pipe-line is not clogged: any obstruction would cause the pump seals to break. WARNING The pump is supplied for use with a two pipe system. For use on a one pipe system, it is necessary to remove the by-pass screw (A), (see figure).
ELECTRICAL WIRING 230V 50Hz WARNING Do not exchange the neutral with the phase. Switch with fuse 6A max. Regulating thermostat Limit thermostat with manual resetting Remote lock-out lamp (230V - 0.5A max.), if required Terminal block of control-box 530SE Valve Black Capacitor Motor...
COMBUSTION ADJUSTMENT In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and testing must be carried out observing the instruction manual of the boiler, including verification of the CO and CO concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.
Page 8
TURN TO THE RIGHT: (sign Fig. 3 In order to increase the volume of air entering the com- bustion chamber and thus diminishing its pressure. There is a reduction of CO and the adhesion of the flame to the air diffuser disc improves. (Setting advisable for ignitions at low temperatures).
ELECTRODES SETTING (See fig. 6) MOVE THE ELECTRODE Attention: Fig. 6 HOLDER BACKWARDS TO Before assembling or remo- 4 ± THE END 0.3 mm ving the nozzle, loosen the screw (A) and move the elec- trodes ahead. D5288 4.5 ± 0.5 mm BURNER START-UP CYCLE Normal...