Contents Declaration....................................3 Information and general warnings............................4 Information about the instruction manual........................4 2.1.1 Introduction ..................................4 2.1.2 General dangers ................................4 2.1.3 Danger: live components ..............................4 Guarantee and responsibility ............................5 Guidance for the use of bio fuel blends up to 30% ......................5 2.3.1 Information and general instructions..........................
Page 4
Contents Electrode setting................................21 Economizer ...................................22 Burner start-up cycle ..............................22 Maintenance ....................................23 Notes on safety for the maintenance..........................23 Maintenance programme ..............................23 9.2.1 Maintenance frequency ..............................23 9.2.2 Maintenance position ..............................23 9.2.3 Checking and cleaning ..............................23 10 Faults / Solutions ..................................25 20032184 (1)
Declaration Declaration Declaration of conformity in accordance with ISO / IEC 17050-1 Manufacturer: RIELLO S.p.A. Address: Via Pilade Riello, 7 37045 Legnago (VR) Product: Gas oil burner Model: G10I These products are in compliance with the following Technical Standard: EN 12100...
Information and general warnings Information and general warnings Information about the instruction manual 2.1.1 Introduction 2.1.3 Danger: live components The instruction manual supplied with the burner: This symbol indicates operations which, if not car- is an integral and essential part of the product and must not ried out correctly, lead to electric shocks with le- be separated from it;...
All components within the hydraulic circuit suitable for manual, operating negligence, incorrect installa- bio fuel use and supplied by Riello will be identified as Bio com- tion and carrying out of non authorised modifica- patible. No warranty is given in relation to the use of components...
Bio fuel delivery. If this is not completed then due to the In no event shall Riello (and its subsidiaries) be liable for any in- hydroscopic nature of Bio fuel, it will effectively clean the...
Safety and prevention Safety and prevention Introduction The burners have been designed and built in compliance with the type and pressure of the fuel, the voltage and frequency of the current regulations and directives, applying the known technical electrical power supply, the minimum and maximum deliveries for rules of safety and envisaging all the potential danger situations.
Bio blend, it will be essential to use flexible oil lines suitable for bio fuel use. Screws and nuts for flange..........No. 4 Please contact Riello for further information. WARNING Screw with two nuts for flange ..........No. 1 Maintenance assembly ............No. 1 External probe..............
Technical description of the burner Burner dimensions Flange Burner D5670 Fig. 2 Firing rate The MAXIMUM OUTPUT is chosen from within the diagram area The work point may be found by plotting a vertical line from the (Fig. 3). desired delivery and a horizontal line from the pressure in the combustion chamber.
Installation Installation Notes on safety for the installation After carefully cleaning all around the area where the burner will The installation of the burner must be carried out be installed, and arranging the correct lighting of the environ- by qualified personnel, as indicated in this manual ment, proceed with the installation operations.
The burner hydraulic components and flexible oil lines must burner technical manual). be suitable for bio fuel use (check with Riello if in doubt). If a Bio blend is in use the installer must seek information Riello have carefully chosen the specification of the bio...
Installation Securing the burner to the boiler Put on the flange 1)(Fig. 6) the screw 2) and two nuts 3). It is necessary that the insulating gasket 5)(Fig. 9) is placed between the boiler door and the burner flange. If necessary, the insulating gasket can be modified as shown in Fig.
Bio blend, it will be essential to use flexible oil lines suitable for bio fuel use. WARNING Please contact Riello for further information. It is strongly recommended a periodic check of the pump pressure operation (annually or better every six months, if the burner operation is contin- uous).
You are advised to use additional filters on the fuel supply line. Riello recommends a good quality fuel filter at the CAUTION tank (Fig. 11) and a secondary filter (60 for gas oil and 15 for kerosene) are used to protect the burner pump and nozzle from contamination.
Usually the tank is lower than the burner. You are advised to use additional filters on the fuel supply line. Riello recommends a good quality fuel filter at the CAUTION tank (Fig. 12 - Fig. 13) and a secondary filter (60 ...
Electrical system Electrical system Notes on safety for the electrical wiring The electrical wiring must be carried out with the electrical supply disconnected. Electrical wiring must be carried out by qualified personnel and in compliance with the regulations currently in force in the country of destination.
Electrical system Electrical wiring Do not swap neutral and phase over, follow the diagram shown carefully and carry out a good earth connection. The electrical wiring carried out by the installer must be in compliance with the rules in force in the country. ...
Electrical system 7.2.1 Control box This operation must be performed with the burner turned off and mains power disconnected. DANGER To remove the control-box from the burner, loosen screw A)(Fig. 15) and pull towards the arrow. S7348 Fig. 15 Run of the electrical cable (Fig. 15) Grommet Cable clamp Terminal block...
Start-up, calibration and operation of the burner Start-up, calibration and operation of the burner Notes on safety for the first start-up The first start-up of the burner must be carried out Check the correct working of the adjustment, com- by qualified personnel, as indicated in this manual mand and safety devices.
Start-up, calibration and operation of the burner Combustion head adjustment This is done when fitting the nozzle, with the blast tube removed. Terminal plane of the blast tube It depends on the output of the burner and is carried out by rotat- ing the regulating rod, till the terminal plane of the blast tube is Shutter level with the set-point, as indicated in the Tab.
Start-up, calibration and operation of the burner Pump pressure and air output The burner is provided with an hydraulic device controlled by the economizer which reduces to approx. 70 % the max. output of gas oil and air. 8.6.1 stage adjustment Adjustment of air shutter Place the small plug 9)(Fig.
Start-up, calibration and operation of the burner Economizer This economizer can be wired to 2 stage thermostat or to an ex- ternal probe. The economizer, connected to the 2 stage thermostat, per- forms two functions: Delay of 5 - 6 seconds in the intervention of the 2 stage valve against 1 stage valve.
Maintenance Maintenance Notes on safety for the maintenance The periodic maintenance is essential for the good operation, Before carrying out any maintenance, cleaning or checking oper- safety, yield and duration of the burner. ations: It allows you to reduce consumption and polluting emissions and to keep the product in a reliable state over time.
Page 26
In case of use with gas oil containing up to 30% Bio blend, it will be essential to use flexible oil lines suitable for bio fuel use. Please contact Riello for further information. WARNING Fuel tank If water or contamination is present within the fuel tank, it is es- sential that this is removed before the equipment is to be used.
Faults / Solutions Faults / Solutions Here below you can find some causes and the possible solutions When lock out lamp lights the burner will attempt to light only after for some problems that could cause a failure to start or incorrect pushing the reset button.