Main Menu Buttons – Settings
The right column of the ADR configuration page is where the occupant adjusts the
operational parameters for ADR. The utility may send up to 3 types of ADR signals to
Skyport. These are: 1) Pricing for the cost of energy, 2) An Offset to the occupants'
comfort setpoints, and 3) a signal to enforce discrete or Static setpoints.
The Maximum Cooling Setpoint and Minimum Heating Setpoints for ADR events are
adjusted here.
The Static Settings are applied when the utility sends a signal to allow the occupant
to enforce their own discrete temperature settings during an ADR event.
The Offset Settings allow the utility to modify the Cool or Heat setpoints by the
value set here during an ADR event.
A Price Trigger setting allows the occupant to set the maximum cost of energy
threshold. When this threshold is exceeded the Price dependent action is enforced.
This Price Trigger and Dependent action is enforced independent of an ADR event,
as long as the utility sends 'real-time' pricing.