Main Menu Buttons – Humidity
This section only applies to the PSP4273CT thermostat
Humidity
IMPORTANT: Aux Output Usage must be set for Hum or
Dehum for these settings to take effect.
See: AUX Output Settings on page

Humidification Settings

Adjust Humidify setpoint. (0% - 60%)
When this step is ON, Humidify will only run with a demand for heat.
When this step is ON, the fan will run with a call for Humidification.

Dehumidification Settings

Adjust Dehumidify setpoint. (25% - 99%)
When this step is ON, the A/C system will be used for Dehumidification.
This specifies how many degrees the A/C system will run past the cool
setpoint to satisfy a demand for Dehumidification. (0 - 20 degrees F)
This turns on electric strip heat during an A/C to dehumidify demand to
help maintain desired room temperatures. (Run A/C to dehumidify must
be set to ON and the GAS ELEC Dip Switch must be set to ELEC -
page 78 - to access this feature).
Run dehumidification only when HVAC calls for A/C.
The Humidity feature allows the thermostat to
control a humidifier or use your air conditioner
to dehumidify the space.
Humidify setpoint
Humidify with heat - OFF
Run fan when humidifying - OFF
Dehumidify setpoint
Run A/C to dehumidify - OFF
Maximum Overcool
Reheat - OFF
79
Dehumidify only when cooling - ON
61.
(0%)
(99%)
(2˚ )