Superior SSDV-3328 Installation Instructions Manual page 18

Direct vent gas fireplace heaters ssdv-3328 series
Table of Contents

Advertisement

VERTICAL VENT FIGURES/TABLES
H
Maximum
H Maximum
+H
1
feet
(meter)
feet
5
(1.524)
2
10
(3.048)
4
15
(4.572)
6
20
(6.096)
8
V + V 1 + H + H 1 = 40 feet (12.2 m) Max
H = 8 feet (2.438 meters) Max.
H + H 1 = 20 feet (6.096 meters) Max.
u
When using Secure Flex, use Firestop / Spacer SF4.5VF
v
When using Secure Flex, use Firestop / Spacer SF4.5HF
Example: If 20 feet total (H+H
then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H+H
maximum total horizontal run of 20 feet.
Figure 29 - Rear Vent - THREE ELBOWS
Table D
H +
Maximum
H
1
feet
(meter)
5
(1.524)
5
(1.524)
10
(3.048)
15
(4.572)
20
(6.096)
H + H
= 20 feet (6.096 m) Max.
1
V + V
+ H + H
= 40 ft. (12.192 m) Max.
1
1
u
When using Secure Flex, use Firestop / Spacer SF4.5VF
v
When using Secure Flex, use Firestop / Spacer SF4.5HF
Figure 30 - Top Vent - THREE ELBOWS
HORIZONTAL (OUTSIDE WALL)
TERMINATION SYSTEM
Figure 31, and Figures 34 to 40 on Pages
21 to 23 and their associated Horizontal Vent
Table illustrate the various horizontal venting
configurations that are possible for use with
these appliances. Secure Vent pipe applications
are shown in these Figures; Secure Flex pipe
may also be used. A Horizontal Vent Table sum-
marizes each system's minimum and maximum
vertical and horizontal length values that can be
used to design and install the vent components
in a variety of applications.
18
(CONTINUED)
Table C
V Minimum
(meter)
feet
(meter)
(0.610)
1
(0.305)
(1.219)
2
(0.610)
(1.829)
3
(0.914)
(2.438)
4
(1.219)
) horizontal vent run is needed,
1
) horizontal run up to a
1
Example: If 20 feet total (H+H
horizontal vent run is needed,
V Minimum
then 4 feet minimum of (V) verti-
cal vent will be required.
feet
(meter)
This table shows a 1(V) to 5(H)
Elbow Only
ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet
1
(0.305)
of (H+H
2
(0.610)
a maximum total horizontal run
of 20 feet.
3
(0.914)
An elbow is acceptable as 1 foot
4
(1.219)
of vertical rise except where
an elbow is the only vertical
component in the system. See
Figure 35.
Both of these horizontal vent systems terminate
through an outside wall. Building Codes limit or
prohibit terminating in specific areas. Refer to
Figure 7 on Page 8 for location guidelines.
Secure Vent SV4.5 direct vent system compo-
nents are unitized concentric pipe components
featuring positive twist lock connection, (refer
to Figure 20 on Page 15). All of the appli-
ances covered in this document are fitted with
collars having locking inclined channels. The
dimpled end of the vent components fit over
the appliance collar to create the positive twist
lock connection.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
v
Spacer (SV4.5HF)
V1
V
)
1
V 1
) horizontal run up to
1
H1
u
Ceiling
Firestop / Spacer
(SV4.5VF)
Wall Firestop/
u
Ceiling
Firestop / Spacer
(SV4.5VF)
H
u
Ceiling
Firestop / Spacer
(SV4.5VF)
H
H 1
A. Plan the vent run -
Analyze the vent routing and determine the
types and quantities of sections required
4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2"
(572 mm), 34-1/2" (876 mm) and 46-1/2" (1181
mm) net section lengths are available. Plan the
vent lengths so that a joint does not occur at the
intersection of ceiling or roof joists. Make allow-
ances for elbows as indicated in Figure 22.
Maintain a minimum 1" (25 mm) clearance to
combustibles on the vertical sections. Clear-
ances for the horizontal runs are; 3" (76 mm)
on top, 1" (25 mm) on sides, and 1" (25 mm)
at the bottom.
v
Wall Firestop/
Spacer (SV4.5HF)
V