Monitoring Your Server - BITMAIN ANTMINER S19 Pro+ Hydro Installation Manual

Table of Contents

Advertisement

4.

Monitoring Your Server

To check the operating status of your server (taking S19 Pro+ Hydro 184T as an example):
Click dashboard marked below to check the server status.
1.
Note: The frequency of S19 Pro+ Hydro server is fixed with the value 505 MHz. Firmware will stop running
when the Temp (PCB) reaches to 75℃ or the water temperature is either greater than 45℃ or lower than
20℃,there will be an error message "Fatal Error: Temperature is too high!" shown on the Bottom of the
Kernel log page.
2.
Monitor your server according to the descriptions in the following table:
Option
Number of chips
Frequency
Real Hashrate
Inlet Temp
Outlet Temp
Chip state
Number of chips detected in the chain.
ASIC frequency setting.
Real-time Hashrate of each hash board (GH/s).
Temperature of the inlet (°C).
Temperature of the outlet (°C).
One of the following statuses will appear:
The Green Icon - indicates normal
The Red Icon- indicates abnormal
- 12 -
S19 Pro+ Hydro Server Installation
Description
4. Monitoring Your Server