Trane RRU150F N Series Installation, Operation And Maintenance Manual page 31

Indirect gas-fired dedicated outdoor air rooftop unit
Table of Contents

Advertisement

Table 4.
RRU UC600 points list
Point
Point
Type
Instance
Point Name
AI
1
S/Air Temperature Local
AI
2
O/Air Temperature Local
AI
3
Outdoor Air RH Local
AI
5
Space RH (Optional)
AI
6
Space Temp (Optional)
AI
7
Space Sp Dial (Optional)
AO
1
Heating Control Signal
AO
2
Combustion Blower Motor
AO
3
OA/RA Damper
AV
1
Space Temp Setpt (BAS)
AV
2
Occ Space Cooling SP
AV
3
Eff Occ Cool SP
AV
4
Eff Occ Heat SP
AV
5
Occ Space Htg SP Offset
AV
6
HGRH Control Deadband
AV
7
Active S/Air Heat SP
AV
8
S/Air Low Temp Cutoff
AV
9
S/Air High Temp Cutoff
AV
10
O/Air Enthalpy
AV
11
Occ Space RH SP
AV
12
Occ S/Air Heating SP
AV
13
Space Cooling SP
AV
14
Active Space Heating SP
AV
15
Y1 - O/A Dehumid Enable
AV
16
Y2 - O/A Dehumid Enable
AV
17
Unocc Space Heating SP
AV
18
Unocc Space Cooling SP
AV
19
Unocc Space RH SP
AV
20
O/Air Heating Enable SP
AV
21
Y1 - O/A Cooling Enable
AV
22
Y1 - Active 0A Dehumid SP
AV
23
Y2- Active 0A Dehumid SP
AV
24
Unocc S/Air Heating SP
AV
25
Htg Failure Temp Deadbnd
AV
26
Htg Failure TD
AV
27
Active O/A Dehum Y1 Enab
AV
28
Active O/A Dehum Y2 Enab
AV
29
S/Air High Cutoff TD
AV
30
S/Air Low Cutoff TD
AV
31
Heat Circuit Timer
AV
32
O/Air Clg Enable Stg1
AV
33
Active O/Air Cool Setpt
AV
34
System Delta T
AV
35
Control Min Time Setup
AV
36
HGRH S/Air Setpoint
AV
37
Space Pressure Setpoint
AV
38
O/Air Dpr Min Position
AV
39
S/Air Min Heat Set Point
RRU-SVX02F-EN
System Configuration and Pre-Start—MP Unit Controller
Value
Unit
Reference
45
°F
UI1.analogValue
30
°F
UI2.analogValue
-24.91
%
UI3.analogValue
0
%
AO1/UI09.analogValue
0
°F
AO2/UI10.analogValue
0
°F
AO3/UI11.analogValue
-10
%
AO4/UI12.analogValue
0
%
AO5/UI13.analogValue
0
%
AO6/UI14.analogValue
0
°F
68
°F
68
°F
64
°F
4
°F
4
°F
72
°F
34
°F
125
°F
7.2
BTU/lb
60
%
72
°F
68
°F
64
°F
28
BTU/lb
36
BTU/lb
50
°F
85
°F
65
%
50
°F
78
°F
28
BTU/lb
0
BTU/lb
80
°F
1.8
°F
5
28
BTU/lb
36
BTU/lb
3
15
0
78
°F
78
°F
15
°F
15
68
°F
0
in(H
O)
2
100
%
45
°F
Active
Priority
Priority Owner
9
BurnerControlIFV48aBacNet
9
BurnerControlIFV48aBacNet
Default
Default
Default
9
ModeandSetpointsDFandIFV48aPart1BacNet
9
ModeandSetpointsDFandIFV48aPart1BacNet
Default
Default
9
SupplyAirSetpointDFandIFV48aBacNet
Default
Default
9
ModeandSetpointsDFandIFV48aPart1BacNet
Default
Default
9
ModeandSetpointsDFandIFV48aPart1BacNet
9
ModeandSetpointsDFandIFV48aPart1BacNet
Default
9
[9, ModeandSetpointsDFandIFV48aPart1BacNet]
[13, User Low]
Default
Default
Default
Default
Default
9
ModeandSetpointsDFandIFV48aPart1BacNet
Default
Default
Default
Default
9
EnthalpySetpointResetDFandIFV48aBacnet
9
EnthalpySetpointResetDFandIFV48aBacnet
Default
Default
9
BurnerControlIFV48aBacNet
Default
9
SupplyAirSetpointDFandIFV48aBacNet
9
FanControlIFV48aBacNet
Default
Default
Default
Default
Default
Rel
Def
25
0
0
0
68
0
0
4
4
60
34
125
0
60
72
70
72
28
34
50
85
65
50
78
0
0
80
1.8
5
26
29
3
15
1
78
78
0
15
68
0
100
45
31