Purging the unit

On delivery, the indoor unit is loaded with an inert Nitrogen gas. All this gas must therefore be purged before
connecting the assembly piping. To purge the inert gas, proceed as follows.
1
Unscrew the caps at the end of each pipe.
Result:
All inert gas escapes from the indoor unit.
• To prevent dirt or foreign objects from getting into the pipes
during installation, do NOT remove the caps completely until you
NOTE
are ready to connect the piping.

Connecting the refrigerant pipe

There are two refrigerant pipes of differing diameters:
f A smaller one for the liquid refrigerant
f
f A larger one for the gas refrigerant
f
f The inside of copper pipe must be clean & has no dust.
f
1
Before connecting the refrigerant pipe, open the cover side.
Remove the pinch pipe on the pipes and connect the assembly pipes
2
to each pipe, tightening the nuts, first manually and then with a torque
wrench, a spanner applying the following torque.
Outer Diameter
ø 6.35 mm
ø 9.52 mm
ø 12.70 mm
ø 15.88 mm
Must apply refrigerant oil on the flaring area to prevent a leak.
NOTE
3
Be sure that there must be no crack or kink on the bended area.
If bracket at right side be disturbed when connecting the pipe, the
installer can detach it by removing 2 screws. But, reassemble plate
NOTE
after connecting the pipe.
8
Torque
kgf•cm
N•m
140~180
14~18
350~430
34~42
500~620
49~61
690~830
68~82
❈ ❈ The designs and shape are subject to change
according to the model.
Refrigerant oil
Torque wrench
Flare nut
Side cover
Spanner
Union