STS PROTOCOL HOLDING REGISTER map (for STATIK TRANSFER SWITCH)
Addr
Parameter
0
SOURCE-1 INPUT VOLTAGE Phase-Neutral (L1)
SOURCE-1 INPUT VOLTAGE Phase-Neutral (L2)
1
SOURCE-1 INPUT VOLTAGE Phase-Neutral (L3)
2
3
SOURCE-2 INPUT VOLTAGE Phase-Neutral (L1)
SOURCE-2 INPUT VOLTAGE Phase-Neutral (L2)
4
SOURCE-2 INPUT VOLTAGE Phase-Neutral (L3)
5
Not used
6
Not used
7
Not used
8
Not used
9
SOURCE-1 INPUT FREQUENCY
10
SOURCE-2 INPUT FREQUENCY
11
12
Not used
Not used
13
Not used
14
15
REFER TO ALARM TABLE.**********
REFER TO ALARM TABLE.**********
16
REFER TO ALARM TABLE.**********
17
REFER TO ALARM TABLE.**********
18
REFER TO ALARM TABLE.**********
19
20
Not used
Not used
21
22
Not used
23
Not used
24
OUTPUT LOAD PERCENTAGE % (L1)
OUTPUT LOAD PERCENTAGE % (L2)
25
26
OUTPUT LOAD PERCENTAGE % (L3)
Not used
27
Not used
28
Not used
29
30
OUTPUT LOAD CURRENT (L1)
OUTPUT LOAD CURRENT (L2)
31
OUTPUT LOAD CURRENT (L3)
32
Not used
33
Not used
34
Not used
35
36
STS CABINET INSIDE TEMPERATURE
37
SYNCHRON ANGLE
Not used
38
Not used
39
Not used
40
41
SOURCE-1 PHASE BALANCE
42
SOURCE-2 PHASE BALANCE
43
L3 ANALOG SYNCHRON DIFFERENCE
Not used
44
Not used
45
Not used
46
Not used
47
48
POWER SUPPLY-1 DC OUTPUT VOLTAGE
49
POWER SUPPLY-2 DC OUTPUT VOLTAGE
- 17 -
MEASUREMENT GROUP (STS PROTOCOL)
Unit
PROTOCOL
V
SRV
SRV
V
SRV
V
V
SRV
SRV
V
SRV
V
Not used
Not used
Not used
Not used
SRV
Hz*10
SRV
Hz*10
Not used
Not used
Not used
Not used
Not used
Not used
Not used
% LOAD
OPL
% LOAD
OPL
% LOAD
OPL
Not used
Not used
Not used
A
OPL
A
OPL
A
OPL
Not used
Not used
Not used
Deg*10
OPL
Deg
OPL
Not used
Not used
Not used
SST
SST
SST
Not used
Not used
Not used
Not used
V
SST
V
SST
Min-max
0-511
0-511
0-511
0-511
0-511
0-511
0-999
0-999
0-255
0-255
0-255
0-511
0-511
0-511
0-511
0-511
0-65535
0-65535
0-511
0-511
0-511