Lynx Smart BMS alarms on the VictronConnect App and a GX device
The following tables list all warning, alarm and error codes:
VictronCo
GX device
nnect
warning
warning
code
code
Low cell
W-B01
voltage
#105 or
W-B02
#106
W-B03
#101
W-B04
#112
W-B06
-
W-D01
#221
W-D02
#222
W-D03
#223
Page 32
Lynx Smart BMS
Message
Low cell voltage
High current
High BMS temperature
Warning bad contactor
Load will disconnect
Communication with distributor A
lost
Communication with distributor B
lost
Communication with distributor C
lost
Instructions / remarks
Charge the battery or reduce the load to prevent an
imminent system shutdown.
Reduce the current to prevent an imminent system
shutdown. Do this by reducing the load or by turning
loads off.
Check the ambient temperature and check if the
BMS fans are running. If the fans are running,
reduce the ambient temperature. If the fans are not
running, contact your Victron dealer.
Reduce the current to prevent an imminent system
shutdown. Do this by reducing the load or by turning
loads off. Contact your Victron dealer.
The loads will be turned off in 30 seconds if fault is
not resolved. For example low battery voltage. This
warning is always in combined the reason why the
load will disconnect.
The loads are turned off via the ATD contact and/or
via the GX device.
Check the cable between BMS and Distributor.
Check the cable between BMS and Distributor.
Check the cable between BMS and Distributor.
Appendix