4.4 Function Parameters

The parameters of SVB Solar Pumping Inverter are grouped by function. For example,
"F07.08" represents the 8th parameter of group F07. The parameters related to solar
pumping inverter are shown in Tab.4-1. The contents of parameter table include:
"Function code": Group number and serial number of the parameter;
"Name": Full name of the parameter;
"Description": Detailed description of the parameter function;
"Setting range": Setting range of the parameter (already pre-treated in the inverter
program to avoid wrong modification)
"Default value": Factory setting value of the parameter. The parameter will be re-
flashed to this value if factory settings are restored while operation state parameter
value or record value will not be flashed.
"Modifiability": Whether or not can the parameter be modified. There are three
kinds of symbol:
: The parameter can be modified in both stop and operation state.
: The parameter cannot be modified in operation state
: The parameter is operation state parameter or record parameter and cannot be
modified (already preprogrammed in the inverter program to avoid wrong
modification)
Function
Name
Code
F00: Basic Function Group
Run/Stop
F00.01
Control Mode
Description
0: Operation panel Run/Stop control mode
(RMT/LOC indicator light off)
Control the run and stop of the pump
through RUN and STOP/RESET keys in
operation panel. Press the above two keys
at the same time can instantly cut off the
inverter voltage output in operation state;
1:Terminal Run/Stop control mode
(RMT/LOC indicator light blinks)
Control the run and stop of the pump
through multi-function DI input terminals
2: Communication Run/Stop control mode
(RMT/LOC indicator light on) Control the
run/stop of the pump from host computer
through communication
4 21
Operating Method
If no water comes out when the pump is operating at 15
Hz (the default value of function parameter F15.19),
please increase the set value of F15.19 until water comes
out to avoid ineffective operation when light is weak
Setting
Default
Range
Value
0~2
1
Modi-
ability