P7 Tests - High Pressure Tests: Unit is run at full capacity without condenser fan running to make sure that the
HPS opens and closes properly.
High Pressure Switch
P7-0
Closed
High Pressure Switch
P7-1
Open
P8 Tests Perishable Mode Tests: Pretrip tests P70 and P71 must have passed or have been skipped for these
tests to execute.
Perishable Mode
P8-0
Heat Test
T-368
Downloaded from
ManualsNet.com
Table 4–7 Controller Pre-Trip Test Codes
With the unit running, the condenser fan is de-energized, and a 15 minute timer is
started. The right display shows discharge pressure if the unit is equipped with a
discharge pressure transducer (DPT). If no DPT is installed, the condenser pres-
sure transducer (CPT) reading will be displayed.
Test is skipped if:
Sensed ambient temperature is less than 7C (45F)
Return air temperature is less than 17.8C (0F)
The water pressure switch (WP) is open, indicating that the unit is operat-
ing with a water-cooled condenser
Test is skipped if the unit does NOT have:
A compressor discharge sensor (CPDS)
A discharge pressure transducer (DPT)
A condenser pressure transducer (CPT)
Test passes if the HPS opens within 15 minutes.
Test immediately fails if the following inputs are sensed to be invalid:
Compressor discharge sensor (CPDS)
Discharge pressure transducer (DPT)
Condenser pressure transducer (CPT)
Return temperature sensor (RTS)
Ambient sensor (AMBS)
Test will also fail if:
HPS fails to open within 15 minutes
Discharge temperature exceeds 138C (280F)
Discharge temperature is less than or equal to ambient temperature plus
5C (9F)
CPT or DPT pressure exceeds 27.42kg/cm
Test P70 must pass for P71 to execute.
The condenser fan is started and a 60 second timer is started.
Test passes if the high pressure switch (HPS) closes within the 60-second time
limit, otherwise, it fails.
If the container temperature is below 15.6C (60F), the set point is changed to
15.6C, and a 60-minute timer is started. The left display will read P80. The control
will then heat the container until 15.6C is reached.
If the container temperature is above 15.6C at the start of the test, then the test
proceeds immediately to test P81 and the left display will change to P81.
The test fails if the 180-minute timer expires before the control temperature reach-
es set point. The display will read P80, FAIL.
search engine
2
4–44
(390psig)