Carrier 69NT40-541-505 Operation And Service Manual page 57

Table of Contents

Advertisement

Code
No.
Dehumidification /
Cd48
Bulb Cargo Mode
Parameter Selection
Display Only Function - Cd49 is a display only function.
Days Since Last
Cd49
Successful Pretrip
Downloaded from
ManualsNet.com
Table 4–5 Controller Function Codes
TITLE
Initially Cd48 will display current dehumidification-mode; bUlb - bulb cargo mode,
dEhUM - normal dehumidification, or OFF - off. This display is steady.
Pressing ENTER key will take the interface down into a hierarchy of parameter se-
lection menus (mode, setpoint, evaporator speed, DTT setting). Pressing ENTER
key in any parameter selection menu commits to selection of the currently dis-
played parameter and causes the interface to descend into the next parameter se-
lection menu. All parameter selection menus alternate between a blank display
and the current selection in the right hand display.
Pressing CODE SELECT key in a selection menu cancels the current selection ac-
tivity and ascends back up to the next higher selection menu (or to Cd48 display
mode if that is the next higher).
If the operator does not press any key for five seconds the interface reverts to nor-
mal system display and the current selection menu is cancelled, but any previously
committed changes are retained.
Available parameters and parameter ranges are a function of configuration options
and previously selected parameters as indicated above.
Whenever any pretrip test is initiated, dehumidification-mode goes to OFF.
Whenever dehumidification-mode goes to OFF:
Dehumidification control setpoint goes to 0% RH internally but will then
initialize to 95% RH when dehumidification-mode leaves OFF.
Evaporator speed select goes to Alt for units without PWM Compressor
Control (Cnf57 = Out), Evaporator speed select goes to Hi for units with
PWM Compressor Control (Cnf57 = In).
DTT setting goes to 25.6°C or 18.0°C, depending on Cnf41.
Whenever dehumidification-mode is set to bUlb, DTT setting goes to 18.0°C if it
had been set higher.
Whenever dehumidification-mode is set to dEhUM, DTT setting goes to 25.6°C or
18.0°C, depending on Cnf41.
For units without PWM Compressor Control (Cnf57 = Out):
Whenever dehumidification control setpoint is set below 65% RH evapo-
rator speed select goes to LO if it had been set to Hi.
Whenever dehumidification control setpoint is set above 64% RH evapo-
rator speed select goes to Alt if it had been set to LO.
For units with PWM Compressor Control (Cnf57 = In):
Whenever dehumidification control set point is set below 60% RH, the
evaporator fan speed is set to LO, the user has the ability to set the evap-
orator fan speed to Hi via the keypad.
Whenever dehumidification control set point is set equal to or above 60%
RH, the evaporator fan speed is set to Hi, the user has the ability to set
the evaporator fan speed to LO via the keypad.
Displays the number of days since last successful pretrip sequence.
Press ENTER to view the number of days since the last successful pretrip for Au-
to1, Auto2, and Auto2 in sequence.
Press CODE SELECT to step back through the list and ultimately to exit the Cd49
display.