Configurable Functions − Cd27 through Cd37 are user-selectable functions. The operator can change the value
of these functions to meet the operational needs of the container.
Defrost Interval
Cd27
(Hours or Automatic)
Temperature Units
Cd28
(Degrees C or
Degrees F)
Cd29
Failure Action Mode
Downloaded from
ManualsNet.com
Table 4–5 Controller Function Codes
TITLE
There are two modes for defrost initiation, either user-selected timed intervals or
automatic control. The user-selected values are (OFF), 3, 6, 9, 12, 24 hours, AU-
TO, or PuLS. Factory default is 3 hours.
Automatic defrost starts with an initial defrost at three hours and then adjusts the
interval to the next defrost based on the accumulation of ice on the evaporator coil.
Following a startup or after termination of a defrost, the time will not begin counting
down until the defrost temperature sensor (DTS) reading falls below set point. If
the reading of DTS rises above set point any time during the timer count down, the
interval is reset and the countdown begins over.
If the DTS fails, alarm code AL60 is activated and control switches over to the re-
turn temperature sensor. The controller will act in the same manner as with the
DTS except the return temperature sensor reading will be used.
If CnF23 is configured to SAv (save), then the value of the defrost interval timer will
be saved at power down and restored at power up. This option prevents short pow-
er interruptions from resetting an almost expired defrost interval, and possibly de-
laying a needed defrost cycle.
Configuration variable (CnF11) determines whether the operator will be allowed to
chose OFF as a defrost interval option.
Configuration variable (CnF64) determines whether the operator will be allowed to
choose PuLS as a defrost interval option. For units operating with PuLS selected,
defrost interval is determined by the unit temperature setpoint and the Evaporator
Fan Pulsing Temperature Setting (Cd60). When the unit temperature setpoint is
equal to or less than the Evaporator Fan Pulsing Temperature Setting, the defrost
interval is set to 6 hours. Otherwise, the defrost interval is determined using the
Automatic Defrost Interval Determination logic. In either case, PuLS remains dis-
played in this function select code.
After a new Defrost Interval is selected, the previously selected Interval is used un-
til the next defrost termination, the next time the DTT contacts are OPEN, or the
next time power to the control is interrupted. If the previous value or the new value
is OFF, the newly selected value will be used immediately.
If any Auto Pretrip sequence is initiated, Cd27 will be set to 'AUTO' unless CnF49
(OEM Reset) is set to Custom AND CnF64 (Evaporator Fan Pulsing Logic) con fig-
uration variable is set to IN, in which case Cd27 will be set to PuLS.
This code determines the temperature units (C or F) which will be used for all
temperature displays. The user selects C or F by selecting function code Cd28
and pushing the ENTER key. The factory default value is Celsius units. This func-
tion code will display ----- if CnF34 is set to F.
This is the desired action to be taken if an alarm occurs that severely limits the ca-
pability of the control system. Depending upon what alarm has occurred, the actual
action taken may not be the same as the desired failure action.
The user selects one of four possible actions as follows:
A - Full Cooling (stepper motor SMV at maximum allowed opening)
B - Partial Cooling (stepper motor SMV 11% open)
C - Evaporator Fan Only
D - Full System Shutdown - Factory Default
search engine
DESCRIPTION
Configurable Functions
The defrost interval timer counts only during compressor run time.
4–23
NOTE
T-368