Technical Data; 24 V - Emergency Supply; Pictogram Explanation - D+H RZN 4404-K V2 Instructions Manual

Hide thumbs Also See for RZN 4404-K V2:
Table of Contents

Advertisement

Technical data

Type
Power supply
Rated power
Stand-by operating
Output voltage
Ripple
Output rated current
Number of lines / groups * 1 / 1
Fire detector per line
SHEV button per line
Current per group **
Mode of operation
- Monitoring
- Alarm / Ventilation
Temperature range
* D+H Highspeed (HS) drives will be supported.
** The total current of the control panel must not be exceeded.
Housing
Material
Colour
Ingress protection
Protection class
Dimensions WxHxD

24 V - Emergency supply

Emergency power supply for 72 hours.
Use VdS approved storage batteries only!
2x 12V / 2,2 Ah ±0,3Ah (Type 2)
With connection of D+H alarm devices:
2x 12V / 3,4 Ah ±0,3 Ah (Type 8)
If the control panel is only operated with a max.
output current of 2 A, the following batteries are
sufficient for the emergency supply:
2x 12V / 1,2 Ah ±0,2Ah (Type 1)
With connection of D+H alarm devices:
2x 12V / 2,2 Ah ±0,3 Ah (Type 2)
99.823.80 3.7/06/19
ZP RZN 4404-K V2
230 V AC, 50 Hz
120 VA
5,8 W
24 V DC
2 Vss, load-dependent
4 A
max. 14 pcs.
max. 8pcs.
max. 4 A
Continuous duty
Short-time duty (30 % DC)
-5 ... +40 °C
GEH-KST
Plastic with steel sheet door
white
IP 30
II, with fuctional ground
310 x 310 x 100 mm
GEH-S-RWA
Steel sheet
light grey
IP 54
I
400 x 300 x 120 mm

Pictogram explanation

SHEV alarm
Malfunction
Control panel O.K.
OK
D+H window drive
Mains existing
Vent button function "OPEN"
Smoke-/ vent button function "CLOSE"
Charging voltage regulator
Ground short
20
40
OPEN running time limitation
sec
2
60
15
30
ventilation time limitation
min
2
45
5/17
RZN 4404-K