Compartments For Future Breakers; Auxiliary/Transition Sections - GE Entellisys Installation And Maintenance Instructions Manual

Low voltage switchgear
Table of Contents

Advertisement

Entellisys Low Voltage Switchgear
Chapter 3. Description
1
1.
Quarter-turn latch
2.
Steel plate (future breaker cubicle)
3-8 Compartments for Future
Breakers
When specified, compartments may be supplied for future
addition of circuit breaker elements. These compartments
are
fully
equipped
with
disconnects, and ancillary devices as required (i.e.
secondary
disconnects,
opening in the breaker compartment door (3),
closed with a bolted-on steel plate (2) to deter accidental
contact with energized electrical circuits. (I.e. primary
disconnect stabs).
Fig. 3-13. Future breaker compartment
drawout
rails,
primary
accessory
devices,
etc.)
3-13, is
Fig.
2

3-9 Auxiliary/Transition Sections

Sections may be provided for any one or more of several
reasons including:
• Transition to a close-coupled transformer
• Incoming cable or busway when a main breaker
The
section is not provided
Auxiliary sections may be 22-inch, 30-inch, or 38-inch
wide as required to accommodate the space requirements.
The compartment doors on the front of the sections are
hinged and latched in the same manner as breaker
compartment doors.
Generally, transition sections will be 22-inches wide for
close-coupling to transformers.
Power company metering requirements generally require
either a 38-inch or 49-inch wide auxiliary section to
accommodate the current transformers, meters, test
switches, etc. as required by their individual practices,
tariff schedules, and/or regulatory commissions.
18
3
3.
Compartment door

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Entellisys and is the answer not in the manual?

Table of Contents