Insulation should be thickened at humid areas. You could follow the procedures of insulating refrigerant
pipes.
(3) Fastening
The insulating tube is just required to be bundled and fastened at the supporting bracket.

6 Electric wiring

6.1 Safety precautions

• The electricians should be licensed.
• The air conditioning is Class I appliances and should be grounded reliably.
• The grounding resistance should comply with the national standards covered in GB 50169
• The yellow-green line is for grounding. Do not use it for other purpose or cut it off or fixed with the
self-tapping screw, other wise it would lead to electric shocks.
• The power supply should be reliably grounded and do not connect the grounding line to a) running
water lines; b) gas lines; c) blow-off lines; d) other unreliable places.
• Do not make the power lines and communication lines entwined and arrange them separately with a
distance no less than 20cm, otherwise it would lead to abnormal communication.
• Do not wire improperly power lines and communication lines. When the power line is wired to the
communication port, it would make the main board burnt out.

6.2 Control concept

External wiring of the electric control cabinet
■ LSQWRF65VM/NaB-X
Unit Installation
NOTE
Romote start/stop
Romote start/stop
81
;
;
;
;