Wiring Terminals; Wiring Diagram - Siemens RWD62U Installation And Commissioning Manual

Hide thumbs Also See for RWD62U:
Table of Contents

Advertisement

Document Number 129-410
October 1, 2004

Wiring Terminals

Wiring Diagram

24 Vac
G
G0
N1
SN
Figure 3. Wiring Diagram.
CAUTION:
The TOOL signal ground is galvanically connected to G0 inside the controller. If the signal line of the
computer is grounded to Earth, the G0 line after TOOL connection will be grounded as well. This will
change the SELV to a PELV.
Page 8 of 10
G
D1 M
X1 M
Y1 M
G0
NOTE:
Screwed terminals for cables with min
2 × 16 or 1 × 14 AWG.
Figure 2. Wiring Terminals.
G
G
B M
B M
X1
X2
S1
X1
M
X2
M
D1
M
TOOL
M
Y1
Y..
G0
G
PC
Y1
RWD62U Controller Installation and Commissioning Guide
X2 M
Tool
Y2
M
M
Y2
Y2
G, G0
24 Vac supply
(SELV 24 Vac power supply)
M
Ground (G0) for signal inputs
and universal inputs
X1
Signal input (main input:
Siemens Ni 1000, Pt 1,000
and 0 to 10 Vdc)
X2
Signal input (Aux. Input:
Siemens Ni 1000, Pt 1000, 0
to 10 Vdc and remote setting
unit)
Y1, Y2
Analog outputs (0 to 10 Vdc)
D1
Digital input
Tool
Communication port with PC
(9-pin plug)
G, G0
Power
N1
RWD62U controller
X1
Room temperature
sensor
(Termination G appears when
X2 is
an active sensor)
X2
Auxiliary sensor or digital input
S1
Time clock or switch
Y1
Heating control valve with
0 to 10 Vdc input
Y2
Cooling control valve with
0 to 10 Vdc input
PC
Personal computer
(optional set-up only)
Siemens Building Technologies, Inc

Advertisement

Table of Contents
loading

Table of Contents