NAME OF PARTS
7.3 CLEARANCE CONDITIONS
?
N O T E
(Unit: mm)
H: Height of the outdoor unit. When L > H, use a base for outdoor unit
to make L ≤ H. Close the base not to allow the outlet air bypassed.
Be sure to use the fan direction guide.
Single
installation
Without
obstacles
on upper
side
Multiple
installation
(two units or
more)
Single
installation
Obstacles
on upper
side
Multiple
installation
(two units or
more)
23
PMML0511 rev.1 - 06/2019
Obstacles on inlet side
300
200
50
200 mm minimum of the back space is acceptable when the right and left sides are open.
Keep both right and left sides without obstacles.
300
100
Keep both right and left sides without obstacles.
When subject to direct sunlight on the back wall, ensure the length B (*) be 500 or greater.
B
B
Keep both right and left sides without obstacles.
100 mm is the minimum space acceptable on the service cover side
when the installation allows an outdoor unit next to other or next to
a wall.
L
A
0 < L ≤ 1/2H
600 or greater
1/2H < L ≤ H
1400 or greater
100
Keep both right and left sides without obstacles.
Serial installation allowed up to two units.
B
300 or greater
350 or greater
B
A
B (*)
A
B
A
B
A