2-5.Connecting Analog Output
Insert the dividing terminal block into the power input/analog output connector to extract the
analog output.
When the dividing terminal block is inserted, the function of each terminal is as follows.
While working for the analog output connection, be sure to shut off power.
Make sure that polarities are correct.
Power supply voltage is specified at DC 12 to 24 V.
When also extracting the analog output, if power is supplied from the AD adapter
connector, be sure not to connect anything to the power input terminal.
Terminal name
FG(grounding)t
Connect to GND
erminal
Connect to DC negative (-) output
DC power(-)
Do not connect anything when using the
adapter
Connect to DC positive (+) output
DC power(+)
Do not connect anything when using the
adapter
Air velocity
negative (-) output of air velocity
output (-)
analog output
Air velocity
positive (+) output of air velocity analog
output (+)
output
Temperature
negative (-) output of temperature
output (-)
analog output
Temperature
positive (+) output of temperature
output (+)
analog output
Humidity
negative (-) output of humidity analog
output (-)
output
Humidity
positive (+) output of humidity analog
output (+)
output
Unused tarminal. Do not connect
NC
anything