Led Indicators - Simplex 4100-6047 Installation And Programming Manual

Building network interface card
Hide thumbs Also See for 4100-6047:

Advertisement

4100-6047 and 4010-9914 Building Network Interface Card Installation and Programming Manual
Jumpers
Jumper P1 sets the Autoforward mode to determine how data traffic is handled before the BNIC CPU is online.
Setting 1-2:
This is the recommended default setting. In this mode the BNIC does not allow traffic to be routed through the switch until the BNIC CPU is online and
running.

LED indicators

Table 3 lists the different LED indicators found on the BNIC that are troubleshooting aids.
LED
Port A (LED 9)
Port B (LED 6)
Port C (LED 2)
Port D (LED 1)
X (LED 5)
Y (LED 4)
Z (LED 3)
Offline (LED 7)
Reset (LED 10) (see Figure 2 for
positioning)
Earth Fault (LED 8)
page 6
Table 3: BNIC LED descriptions
Description
Port Status LED
Card Status LED
Offline Indication
Reset Indication
Earth Fault Indication on Port A
Figure 5: LED positioning
Signification
OFF = No Connection
ON Steady = Non-active connection
ON Blinking = Active connection
Used for manufacturing and development only, not used for installed BNIC
ON = Offline (not communicating with 4100ES Master Controller Card)
OFF = Normal Operation
ON = BNIC is in reset
Off = Normal Operation
ON = Earth Fault detected on Port A
OFF = No Earth Fault detected