PSP Hurricane 5000 NEMA 4X Series Installation

Advertisement

Hurricane 5000 NEMA 4X Series Installation
HxC 100 / 300 / 400 Models
1. Preparation for install of Surge Suppressor
a. Verify the system voltage and wiring configuration is the same as the enclosed model HxC 100/300/400 by checking it against the
product label located on the front cover of the enclosure.
b. Review the installation area to ensure the proper space is available to properly mount and install the HxC 100/300/400. The enclosure
should be mounted no more than 3 feet away from the distribution panel.
c. Check that the buildings facility grounding system meets all NEC & CEC requirements as well as local codes. A low resistance ground
system is essential to the proper functioning of any surge suppression device. The soil resistance level should be no more than 25 ohms. This
can be verified by performing a soil resistivity test.
H1Cxxx-4X-MHW(D)
H2Cxxx-4X-MHW(D)
H3Cxxx-4X-MHW(D)
H9Cxxx-4X-MHW(D)
H4Cxxx-4X-MHW(D)
H6Cxxx-4X-MHW(D)
H5Cxxx-4X-MHW(D)
2. Location of Surge Suppressor
a. For service entrance applications, install the suppressor at the main distribution panel on the load side after the main disconnect. Ensure
that the enclosure's hinged door can be opened and closed without interference from the surrounding area. This is to provide internal
access to the device if necessary. IMPORTANT! Remember to keep conductor lead length to a minimum; 3ft or less.
b. For Feeder/Sub-panel applications, install the suppressor directly adjacent to the panelboard. Ensure that the enclosure's hinged door
can be opened and closed without interference from the surrounding area. This is to provide internal access to the device if necessary.
IMPORTANT! Remember to keep conductor lead length to a minimum; 3ft or less.
3. Wiring of Surge Suppressor
a. TURN OFF the power to the distribution panel where the model HxC 100/300/400 will be installed.
b. Install a circuit breaker to feed the model HxC 100/300/400 surge suppressor. This will allow safety personnel to remove power from the
device in order to diagnose or service the unit. In addition, the device incorporates internal fusing, UL & CSA approved, that will protect
against short circuit fault conditions within the unit.
II. A circuit breaker is not required for installation of model HxC 100/300/400's with integral disconnect switches.
c. Install either a rigid or flexible metal conduit between the model HxC 100/300/400 and the distribution panel.
d. Run wires from the distribution panelboard to the terminals of the model HxC 100/300/400.
e. Strip the ends of the wire and terminate within the model HxC 100/300/400 terminals and panelboard.
www.pspproducts.com
Model
120/208VAC, 3Ø, 4W+G, Wye
120/120/240VAC, 3Ø, 4W+G, Hi-Leg Delta
277/480VAC, 3Ø, 4W+G, Wye
347/600VAC, 3Ø, 4W+G, Wye
I. A time delay fused disconnect switch can be used in lieu of circuit breaker.
Phone: 800-648-6802
PSP Products Inc. - 8535 Phoenix Drive, Manassas, VA 20110
System
120/240VAC, 1Ø, 3W+G
240VAC, 1Ø, 3W+G, Delta
480VAC, 1Ø, 3W+G, Delta
Notes:
sales@pspproducts.com
Wire Diagram
[pg.4]
Fig. 1
Fig. 4
Fig. 2
Fig. 4
Fig. 3
Fig. 3
Fig. 4
Fax: 703-393-9101
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Hurricane 5000 NEMA 4X Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for PSP Hurricane 5000 NEMA 4X Series

  • Page 1 Run wires from the distribution panelboard to the terminals of the model HxC 100/300/400. e. Strip the ends of the wire and terminate within the model HxC 100/300/400 terminals and panelboard. www.pspproducts.com Phone: 800-648-6802 sales@pspproducts.com Fax: 703-393-9101 PSP Products Inc. - 8535 Phoenix Drive, Manassas, VA 20110...
  • Page 2 Wire Size Circuit Breaker #12 AWG 20A rms 30A rms #10 AWG #8 AWG 50A rms #6 AWG 60A rms www.pspproducts.com Phone: 800-648-6802 sales@pspproducts.com Fax: 703-393-9101 PSP Products Inc. - 8535 Phoenix Drive, Manassas, VA 20110...
  • Page 3: Wiring Diagrams

    Figure 3 Figure 4 Surge protector Surge protector for Wye Systems for Delta Systems 3ph, 4W+G, Wye 3ph, 3W+G, Delta 120/208 220/380 240/415 277/480 347/600 www.pspproducts.com Phone: 800-648-6802 sales@pspproducts.com Fax: 703-393-9101 PSP Products Inc. - 8535 Phoenix Drive, Manassas, VA 20110...
  • Page 4: Mounting Dimensions

    Hurricane 5000 NEMA 4X Series Installation 6. Mounting Dimensions HxC 200 15.7 [400] 11.8 [300] [180] Mounting Dimensions (Cont.) HxC 400 and HxC 600 19.7 [500] 15.7 [400] [185] www.pspproducts.com Phone: 800-648-6802 sales@pspproducts.com Fax: 703-393-9101 PSP Products Inc. - 8535 Phoenix Drive, Manassas, VA 20110...
  • Page 5: 10 Year Limited Warranty

    PSP Products disclaims liability for any incidental, indirect, special or consequential damages arising out of the sale or use of any PSP products (including without limitation lost business profits, loss of data and all freight, mileage, travel time and insurance charges associated with warranty coverage claims).

Table of Contents