3.46"
Installation Instructions
1.
Confirm device is rated for your system by
comparing voltage measurements to the line
voltage on the product label.
2.
Turn off all power supplying this equipment
before working on or inside the equipment.
3.
See installation diagrams below and match to
your specific installation type.
4.
If installing on a breaker, use a 20A-60A breaker
and verify lug on breaker provides solid connection
to SPD wiring.
5.
In some jurisdictions, provided flat tabs can be
used in the bottom of the lug.
6.
As a Type 1, no breaker is required.
7.
Install in accordance with all pertinent articles of
the National Electric Code.
8.
Confirm that the electrical terminals used
to attach this device are identified for
these conductors.
9.
Keep conductor length as short as possible
with no sharp bends.
10. Do not loop or coil wires.
11. Ensure a high quality ground is in place.
12. Turn on all power supplying this equipment.
13. Verify diagnostic indicator is illuminated and no
audible alarm is present.
14. Install cover and/or close door on
equipment fixture.
Technical Assistance: 703-687-4057
Important: Risk of electrical shock.
This device should only be installed by qualified personnel.
3.46"
3.46"
Installation Notes
Designed to allow installation inside of electrical panel using optional L-bracket.
Designed to allow installation inside of a finished wall using optional flush mount cover.
Diagram A Type 1 Installed on
Occupied Breaker
Ground
Neutral
Load
connection
Panel and Equipment Surge Protector
IMPORTANT:
FLAT BLADE TERMINALS
MUST BE INSTALLED UNDER MAIN
CONDUCTOR AND NOT BETWEEN THE
CONDUCTOR AND LUG SCREW TERMINAL
TO CONFORM TO PROPER INSTALLATION
STANDARDS. USE ONLY THE TERMINALS
SUPPLIED, IF TERMINALS ARE DAMAGED
OR MISSING CONTACT PSP PRODUCTS
FOR REPLACEMENTS.
Diagram B Internal
Panel Mount
Install small L-bracket
inside of the electrical
Ground
Neutral
panel. Insert nipple
through L-bracket and
secure with locknut.
Device may be secured
alternatively using double
sided tape, when placed
at the bottom of the panel.
See diagram A for wiring
instructions, depending on
your application.
N
Optional
G
Mounting
Bracket
PSP Products | 8618 Phoenix Drive, Manassas, VA 20110
pspproducts.com | 703.687.4057 | sales@pspproducts.com
Category 2 Hurricane
GOOD
X
BAD
replace
Diagnostic Operation
LED ON = Normal operation
LED OFF (one or more) = Fault,
check phase, check voltage &
connections. If OK, replace unit.
Audible Alarm ON = check phase
Diagram C Type 1 Install: Transfer Switch with
Piggyback Connectors or Ring Terminals
Ground
LINE
GEN LINE
LOAD
Optional Connection: Surge
Optional Connection:
Protector may be connected
SPD may be connected to
to Line or Load side of
LINE or LOAD side of ATS
transfer switch.
9.26.24

Advertisement

loading
Need help?

Need help?

Do you have a question about the Category 2 Hurricane and is the answer not in the manual?

Questions and answers

Summary of Contents for PSP Category 2 Hurricane

  • Page 1 14. Install cover and/or close door on equipment fixture. Technical Assistance: 703-687-4057 PSP Products | 8618 Phoenix Drive, Manassas, VA 20110 Important: Risk of electrical shock. pspproducts.com | 703.687.4057 | sales@pspproducts.com This device should only be installed by qualified personnel.
  • Page 2 Lifetime Product Coverage PSP will, at its sole discretion, repair or replace any Category 2 Hurricane Surge Protection Device (SPD) that is defective or is damaged by an electrical surge (including those caused by distant lightning) for the lifetime of the product from the date of the installation by the original owner or owner of record of premises.

This manual is also suitable for:

Ev100