Kyoritsu Electrical Instruments Works KEW3431 Instruction Manual

Kyoritsu Electrical Instruments Works KEW3431 Instruction Manual

Compact insulation resistance tester

Advertisement

Quick Links

Instruction Manual
Compact Insulation resistance tester
KEW3431

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KEW3431 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Kyoritsu Electrical Instruments Works KEW3431

  • Page 1 Instruction Manual Compact Insulation resistance tester KEW3431...
  • Page 2: Table Of Contents

    Contents 1. Safety warnings ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 1 2. Features  ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 5 3. Specifications  ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 6 4. Instrument layout ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 9 5. Accessories  ・ ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 11 6. Getting started ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 12    6-1 Mechanical zero adjustment  ・ ・・・・・・・・・・・・・・・・・・・ 12    6-2 Attaching metal tip/ adapter to test leads  ・ ・・・・・・・ 12    6-3 Battery voltage check・・・・・・・・・・・・・・・・・・・・・・・・・・ 13 7.Voltage measurement  ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 14    7-1 Measurement method  ・ ・・・・・・・・・・・・・・・・・・・・・・・・・ 14 8. Insulation resistance measurement ・・・・・・・・・・・・・・・・・・・・・ 15    8-1 Measurement method  ・ ・・・・・・・・・・・・・・・・・・・・・・・・・ 18    8-2 Continuous measurement ・・・・・・・・・・・・・・・・・・・・・・...
  • Page 3: Safety Warnings

    1. Safety warnings This  instrument  has  been  designed,  manufactured  and  tested  according  to  IEC  61010:  Safety  requirements  for  Electronic  measuring  apparatus,  and  delivered  in  the  best  condition  after  passing quality control tests.  This  instruction  manual  contains  warnings  and  safety  rules  which  have  to  be  observed  by  the  user  to  ensure  safe  operation  of  the  instrument ...
  • Page 4 # DANGER ●  N ever  make  measurements  on  circuits  in  which  earth  potentials  higher than 600 V exist. ●  K EW3441 is a CAT III-rated instrument. Do not make measurements  under  the  circumstances  exceeding  the  designed  measurement  category. ●  D o  not  attempt  to  make  measurements  in  the  presence  of  flammable  gasses.  Otherwise  the  use  of  the  instrument  may  cause sparking, which can lead to an explosion.
  • Page 5 # CAUTION ●  A lways  make  sure  to  set  the  function  switch  to  the  appropriate  position before making a measurement.  ●  P ower  off  the  instrument  after  use.  Remove  batteries  if  the  instrument is to be stored and will not be in use for a long period. ●  D o not expose the instrument to direct sunlight, high temperature,  humidity or dew. ●  U se a damp cloth with neutral detergent or water for cleaning the  instrument. Do not use abrasives or solvents. ●  T his  instrument  is  not  water-proof.  Do  not  let  the  instrument  get  wet with water; otherwise it may cause malfunction. ...
  • Page 6 Measurement Category      T o  ensure  safe  operation  of  measuring  instruments,  IEC  61010  establishes  safety  standards  for  various  electrical  environments,  categorized  as  O  to  CAT  IV,  and  called  measurement  categories.  Higher-numbered  categories  correspond  to  electrical  environments  with  greater  momentary  energy,  so  a  measuring  instrument  designed ...
  • Page 7: Features

    2. Features KEW3431  can  measure  insulation  resistance  and  also  AC/DC  voltage on low-voltage installations of 600V or less. ●Designed to meet the following safety standards    IEC 61010-1, IEC 61010-2-030 CAT III 600V Pollution degree 2    IEC 61010-031 ●Compact and lightweight design ●  S cale  light  and  LED  spot  light  to  facilitate  working  at  dimly  illuminated  location  or  at  nighttime  work.  Built-in  illuminance  sensor  automatically  turns  on  off  the  lights.  Auto-light-off  function ...
  • Page 8: Specifications

    3. Specifications ●Measuring range and accuracy(23ºC±5ºC, RH 85% or less) [Voltage measurement] Measurement  0 〜 600V voltage Accuracy within ± 5% of the maximum scale value    ※  F or an input voltage of 30V or more, the instrument automatically  judges AC or DC and indicates the result with the LED.       For AC voltage: Red LED lights up.       For DC voltage: Orange LED lights up.     (The LED doesn t light up if input voltage is less than 30V.) [Insulation resistance measurement] Rated measurement 250V 500V 1000V voltage Max. effective scale  200MΩ 200MΩ 2000MΩ value Accuracy in first  0.1 to 100MΩ 1 to 1000MΩ effective measuring  within ± 5% of indicated value ranges Accuracy in second  within ± 10% of indicated value  effective measuring  ※  m easuring  ranges  other  than  above,  0  and  ranges ∞ ticks Accuracy at 0 & ∞...
  • Page 9 ●Applicable ●IEC 61010-1, 2-030 CAT III 600V     standards    Pollution degree 2 ●IEC 61557-1, -2 ●IEC 60529 IP40 ●IEC 61326-1, 2-2 ●IEC 61010-031  MODEL7260…CAT III 600V (w/ cap)          CAT II 1000V (w/o cap)          CAT II 1000V (w/ 8017A)  (  A ttach the supplied protective cap to use this  test leads in CAT III or higher environments.)  MODEL7261A…CAT III 600V (w/ alligator clip)          CAT II 600V (w/ flat test bar)  (  A ttach the alligator clip to use this test leads  in CAT III or higher environments.) ※  W hen  test  probes,  sometimes  with  metal  tips,  are  connected  and  used  with  the  instrument,  the  measurement  category  and  voltage  rating  of the lowest rated item is applied.
  • Page 10 ●Operating uncertainty (IEC 61557-2)    O perating  uncertainty  (B)  is  an  error  obtained  under  the  nominal  operating  conditions,  and  calculated  with  the  intrinsic  error  (A),  which is an error of the instrument used, and the error (En) due to  variations. According to IEC61557-2, the maximum operating error  should  be  within  ±  30%.  Intrinsic  error  (A)  is  uncertainty  of  the  performance  characteristics  of  insulation  resistance  testers  in  the  reference condition.
  • Page 11: Instrument Layout

    4. Instrument layout (1) Front panel   ⑤ ⑥ ⑦ ⑤ ④ ⑧ ③ ⑨ ② Fig. 4-1 ① ⑩ Name Description ① Meter zero adjuster Adjusts the pointer position. ② Pointer Indicates the measured values. Starts/  stops  measurement.  For  continuous  ③ Test button measurement,  press  and  turn  the  button  clockwise to lock it in the operating position. Detects  ambient  brightness  to  turn  on/  off  ④...
  • Page 12 Indicates battery voltage level. LED battery status  Solid green  : Enough ⑨ indicator Blinking green  : Low Solid red    : Almost exhausted  Switches  measurement  functions  and  selects  ⑩ Function switch voltage for insulation resistance measurement. (2) Side panel ③ ① ② Fig. 4-2 Name Description ① LINE Terminal for MODEL7260 test lead ② EARTH Terminal for MODEL7261A test lead Illuminates  the  point  to  be  measured.  The  light  ③...
  • Page 13: Accessories

    5. Accessories ●Test leads (1) Test lead MODEL7260 with remote control switch (red) ※1 Barrier Metal tip Rating  of  measurement  category  of  the  test  lead  depends  on  attaching/  Insulation cap removing the insulation cap.  CAT III 600V (w/ cap) Fig. 5-1  CAT II 1000V (w/o cap) (2) Extension prod MODEL8017A    ※Attached and used with MODEL7260. Long type and helpful to access  the distant measurement spot Fig. 5-2 (3) A set of test leads with alligator clip MODEL7261A  Black cord with banana plugs at both ends L-shaped Banana plug +      Alligator clip           Flat test bar ※1 Barrie ※1 Barrier +...
  • Page 14: Getting Started

    6. Getting started 6-1 Mechanical zero adjustment With  the  function  switch  set  to  OFF  position  and  without  pressing  the  test  button,  turn  the  zero  adjuster  with  a  screwdriver  so  that  the  pointer  lines  up  with  the ∞ mark  on  the  insulation  resistance  scale.  In  case  the  instrument  is  used  at  sloping  place,  ensure  that  the ...
  • Page 15: Battery Voltage Check

    To  avoid  getting  electrical  shocks,  ensure  that  test  leads  are  disconnected  from  the  instrument  when  replacing  the  metal  tip  or  adapter for test leads. 6-3 Battery voltage check (1)   P lease  refer  to 11.  Battery  replacement in  this  manual  and  insert batteries in KEW3431. (2)   S et the function switch to any position other than OFF to power  on theinstrument. (3) Check the color of LED battery status indicator.       Solid green : Battery voltage is enough.
  • Page 16: 7.Voltage Measurement

    7. Voltage measurement # DANGER ●  D o  not  apply  a  voltage  exceeding  the  maximum  allowable  input  (600V) to the instrument. ●  K eep your fingers behind the barrier during a measurement. ●  V erify  proper  operation  on  a  known  source  before  taking  actions  as a result of the indication of the instrument 7-1 Measurement method Set the function switch to V  position to measure voltage. AC/DC (1) Connect the test leads as the following figure shows.    ・MODEL7260 to Line terminal   ・MODEL7261A to Earth terminal Fig.
  • Page 17 (3)   C heck the reading on the LCD without pressing the test or remote  control  button.  The  instrument  detects  AC/DC  automatically,  and turns on the red LED for ac input and the orange LED for dc  input.   ・  W hen  the  measured  voltage  is  less  than  30V,  AC/DC  auto- detect doesn t work. # CAUTION The pointer sweeps depending on the applied input even while the  instrument is powered off; however, accuracy is not guaranteed. In  this state, live warning LED doesn t light up. Ensure the instrument  is powered on to measure voltage. ̶  15  ̶...
  • Page 18: Insulation Resistance Measurement

    8. Insulation resistance measurement This  instrument  is  used  to  measure  insulation  resistance  in  electric  appliance or circuit to inspect the insulation performance. Check the  voltage rating of the object to be tested before making measurement  and select the voltage applied to. Note:  ●  D epending  on  the  object  to  be  measured,  displayed  insulation  resistance value may not stabilize.  ●  T he  instrument  may  give  bleep  during  an  insulation  resistance  measure-ment, however, this is not a malfunction.
  • Page 19: Measurement Method

    8-1 Measurement method (1) Connect the test leads as the following figure shows.    ・MODEL7260 to Line terminal   ・MODEL7261A to Earth terminal Fig. 8-1 Black (2)   C onfirm  the  circuit  under  test  is  not  energized,  and  measure  voltage with reference to 7. Voltage measurement . (3)   C onfirm  the  voltage  value  which  can  be  applied  to  the  object  under test, and then set the function switch to a desired range.      ●  T here is an empty range between 500V and 1000V for safety  purpose.  If  the  function  switch  is  set  to  this  safety  position,  the instrument doesn t start a measurement although the test ...
  • Page 20 Principle of insulation resistance measurement Resistance Value=Voltage/Current Fig. 8-2 RX=V/I Fig. 8-3 (6) Auto discharge function    T his  function  allows  electric  charges  stored  in  the  capacitance  of  the  circuit  under  test  to  be  automatically  discharged  after  measurement.  Set  the  test  button  or  remote  control  switch  to  off  with the test leads connected. Discharge can be checked with the ...
  • Page 21: Continuous Measurement

    ●Dual scale    R ead insulation resistance on the outer and inner scale depending  on the range used for testing.  Use the outer scale for the testing on this range. Use the inner scale for the testing on these ranges. # DANGER Never  touch  the  circuit  under  test  immediately  after  measurement. Capacitance  stored  in  the  circuit  may  cause  electric  shock.  Leave  the test leads connected to the circuit and do not touch the circuit ...
  • Page 22: Output Voltage Characteristics

    8-3 Output voltage characteristics This  instrument  conforms  to  IEC61557.  This  standard  defines  that  the  nominal  current  shall  be  at  least  1mA,  and  the  lower  limit  of  the  insulation  resistance  maintaining  the  nominal  voltage  at  the  measurement  terminal.  (See  the  graph  below.)  This  value  is  calculated ...
  • Page 23: Led Insulation Status Indicator

    8-4 LED insulation status indicator KEW3431  has  insulation  status  check  function.  In  an  insulation  measure-ment,  the  measured  value  is  compared  to  the  pre-set  reference  value,  and  either  red  or  green  LED  lights  up  according  to  the result. This function can be turned off. See 10. How to disable  LED  insulation  status  indicator  &  auto-lighting in  this  manual  for ...
  • Page 24: Scale Light And Led Light

    9. Scale light and LED light The  illuminance  sensor  on  this  instrument  detects  ambient  brightness  andautomatically  turns  on/  off  the  scale  light  and  LED  light. Once these lights turn on, they stay on for about 15 sec. This  auto-lighting  function  can  be  turned  off.  See 10.  How  to  disable  LED  insulation  status  indicator  &  auto-lighting in  this  manual  for  detail.
  • Page 25: How To Disable Led Insulation Status Indicator & Auto-Lighting

    10. How to disable LED insulation status indicator & auto-lighting 1.   G et  the  instrument  into  configuration  mode,  to  disable  the  LED  insulation status indicator and auto-lighting of scale light and LED  light. (1)   C over the illuminance sensor with your finger and turn the function  switch from OFF to V  position and power on the instrument. AC/DC (2)   P ress  the  test  button  five  times  within  three  seconds  after  the  LED ...
  • Page 26 Blinks when“ON” has been selected for LED insulation status Blinks when“ON” indicator. has been selected for scale light / LED light. Fig. 10-2 3.   T he  instrument  exits  from  configuration  mode  when  it  is  powered  off butretains the selected setting.  It  may  difficult  to  get  the  instrument  in  configuration  mode  in  outdoor even the sensor is covered with your finger.
  • Page 27: Battery Replacement

    11. Battery replacement Replace  batteries  with  new  ones  when  the  red  LED  battery  status  indicator lights up. # DANGER ●  D o not open the battery compartment cover if the instrument is wet. ●  N ever attempt to replace batteries during a measurement. In order  to  avoid  getting  electrical  shock,  ensure  that  the  instrument  is  powered off and test leads are disconnected from the instrument  before replacing batteries.  ●  T he  battery  compartment  cover  must  be  closed  and  screwed  before ...
  • Page 28: Shoulder Strap Belt Attachment

    12. Shoulder strap belt attachment This instrument is equipped with a strap to suspend from the neck to  allow both hands to be used freely for easy and safe operation. Fig. 12-1 ̶  26  ̶...
  • Page 29: Storing In Carrying Case

    13. Storing in Carrying case Store the instrument and test leads as the following figure shows. Test leads compartment Partition Unit compartment Fig. 13-1 # CAUTION Ensure  that  the  instrument  is  powered  off  before  storing  in  the  carrying case. ̶  27  ̶...
  • Page 30: Cleaning Meter Cover

    14. Cleaning meter cover This instrument is managed by our company s quality standard and is  delivered in the best condition after passing the inspection. But in the  dry time of winter static electricity sometimes builds up on the meter  cover due to the characteristics of plastic. When  static  builds  up  on  the  meter  cover  and  affects  the  meter  reading,  use  a  cloth  damped  with  off-the  shelf  anti-static  agent  or  detergent to wipe the meter cover surface.  # CAUTION ●  W hen  the  pointer  deflects  by  touching  the  surface  of  this  instrument or zero adjustment cannot be made, do not try to make ...
  • Page 32 DISTRIBUTOR Kyoritsu  reserves  the  rights  to  change  specifications  or  designs  described in this manual without notice and without obligations. 3-19 92-2297A...