Sensor And Equipment Connections; Input Connections; Output Connections - KMC Controls FlexStat BAC-19 Series Installation Manual

Hide thumbs Also See for FlexStat BAC-19 Series:
Table of Contents

Advertisement

NOTE: The S (Shield) terminal in KMC
controllers is provided as a connecting
point for the shield. The terminal
is not connected to the ground of
the controller. When connecting to
controllers from other manufacturers,
verify the shield connection is not
connected to the controller's ground.
EOL
MS/TP
EOL On
EOL Off
ON
+B
EOL Switches
–A
Pushed Up
EOL Switches
+B
Pushed Down
–A
OFF
ON
+B
EOL Switches
–A
Pushed Up
Illustration 10—MS/TP Connections and EOL (MS/TP Models)
2. Connect the cable shield to a good earth
ground at one end only.
NOTE: Devices on physical ends of MS/TP
wiring segments must have EOL (End
Of Line) termination for proper network
operation. Verify the FlexStat's EOL
switch is in the proper position.
3. If a FlexStat is at the physical end of the MS/
TP network line (only one wire on each –A or
+B terminal), set both EOL switches to On on
the back of the circuit board. If not on the end
of the line (two wires on each terminal), ensure
that both switches are Off.
BAC-19xxxx FlexStat Installation Guide
EOL Off
EOL On
Shield Wire
Not Connected
Shield Wires
Connected
with Wire Nut
Shield Wire
Connected to
Ground (on
One End Only)

SENSOR AND EQUIPMENT CONNECTIONS

Input Connections

1. Wire any additional sensors to the appropriate
input terminals. See the
Sequence of Operation and Wiring
(These applications are the selectable pack-
aged programs in the BAC-19xxxx models.)
NOTE: Use KMC software to properly
configure the devices. For passive
input devices (e.g., switch contacts
and 10K ohm thermistors), set the
termination to the 10K Ohm position.
For active voltage devices, set it to the
0 to 12 VDC position.
NOTE: Unused analog inputs can be
converted to binary inputs by right-
clicking the input object in KMC
software and selecting Convert to....
NOTE: Wire sizes 14–22 AWG can be clamped
in each terminal. No more than two 16
AWG wires can be joined at a common
point.

Output Connections

1. Wire additional equipment (such as fans,
dampers, and valves) to the appropriate out-
put terminals. See the
Sequence of Operation and Wiring
Connect the device under control between
the desired output terminal and the related
SC (Switched Common for relays) or GND
(Ground for analog outputs) terminal.
One Switched
Common
Connection in
Bank of Three
Normally
Open Relays
Illustration 11—Switched (Relay) Common and Relay Bank
NOTE: For the bank of three relays, there
is one Switched (relay) Common
connection (in place of the GND
terminal used with analog outputs).
5
BAC-19xxxx FlexStat
Guide.
BAC-19xxxx FlexStat
Guide.
Relay 3
SC (Phase) 1–3
Relay 2
Relay 1
926-019-02C

Advertisement

Table of Contents
loading

Table of Contents