2-6. E: 26.X. Address setting error in wired remote controller
(Indoor unit)
Indoor unit
Indicator
outdoor unit
→ired remote controller (2-wire)
Detective actuator
Indoor unit controller PCB
Forecast of cause
Check point 1. →ire installation
Check the wire connection in the remote controller group (For installation method, refer to in-
stallation manual)
-> If there is an abnormal condition, correct it by refer to the installation manual or the "DESIGN
& TECHNICAL MANUAL".
Check point 2. →rong remote controller group setting
The given address number by auto setting (00) and the manual set number (except 00) are not
existing in one remote controller group.
The remote controller address setting by UI is not existing same address.
The duplicate address number is not existing in one remote controller group.
Check point 3. Check indoor unit main PCB
Check if main PCB is damaged.
Change main PCB and check the error after setting remote controller address.
2-6. E: 26.↓. Address setting error in wired remote controller (Indoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
End
Continuous flash
Refer to
"Error code table (Outdoor unit)"
→hen the address number set by auto setting and
manual setting are mixed in one remote controller
group
→hen the duplicated address number exists in one
remote controller group
→rong wiring of remote controller group
→rong remote controller address setting
Indoor unit main PCB failure
Remote controller failure
- (03-20) -
2 time flash
6 time flash
E: 26
on page 03-4