Inverter Compressor - Fujitsu ASUH18LMAS Service Manual

Wall mounted type
Hide thumbs Also See for ASUH18LMAS:
Table of Contents

Advertisement

5-2. Inverter compressor

Check point 1. Check connection
Check terminal connection of compressor (loose or incorrect wiring)
Check terminal connection of main PCB (loose or incorrect wiring)
Check point 2. Check winding resistance
Check winding resistance of each terminal.
Resistance value: 1.160 Ω ±8 % 68 °F (20 °C)
T(W)
If the resistance value is 0 Ω or infinite, replace compressor.
Check point 3. Replace inverter PCB
If check point 1 to 2 do not improve the symptom, replace main PCB.
5-2. Inverter compressor
S(V)
(WHITE)
Main PCB
R(U)
(RED)
Main PCB
W400(U) W401(V)
RED
Compressor
RED
R(U)
WHITE
S(V)
BLACK
- (03-81) -
T(W)
(BLACK)
W402(W)
BLACK
WHITE
5. Service parts information

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Asuh24lmasAouh18lmas1Aouh24lmas1

Table of Contents