Fujitsu ASUH18LMAS Service Manual page 211

Wall mounted type
Hide thumbs Also See for ASUH18LMAS:
Table of Contents

Advertisement

 Auxiliary heat pump control by outdoor temperature 2
• External heater output
Operation
Heater on
Heater off
– Temperature of heater on (Thon): Set temperature (Ts) - 0.9 °F (- 0.5 °C)
– Temperature of heater off: Set temperature (Ts) + 0.9 °F (+ 0.5 °C)
Tr-Ts ≥ 0.9°F
(0.5°C)
• Auxiliary heat pump On/Off
– Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of heat pump).
– All control temperatures will shift by adjusting "Thon".
Tr-Ts ≥ -1.8°F
(-1°C)
• Outdoor temperature zone
B + 3.6°F (2°C): 46.4°F (8°C)
*: Adjustable by function setting 67
2-4. Details of function
Heater is on as shown in following diagram of heating temperature.
Heater is off as shown in following diagram of heating temperature.
Other than heating mode
Error occurred
Forced thermostat off
Tr-Ts
Off
Tr-Ts (=Thon) ≤ -0.9°F (-0.5°C)
On
Tr-Ts
Off
Tr-Ts (=Thon) < -5.4°F (-3°C)
On
Outdoor temp.
Heater only zone
*B: 42.8°F (6°C)
Combination zone
(Heat pump + Heater)
Condition
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
- (05-37) -