1. Error code

1-1. Error code table (Indoor unit and wired remote controller)

The operation, timer, and economy indicators operate according to the error contents.
For confirmation of the error contents, refer the flashing pattern as follows.
Error contents
E: 11. Serial communication error (Serial
reverse transfer error) (Outdoor unit)
E: 11. Serial communication error (Serial
forward transfer error) (Indoor unit)
E: 12. Wired remote controller
communication error (Indoor unit)
E: 18. External communication error (Indoor
unit)
E: 22. Indoor unit capacity error (Indoor
unit)
E: 23. Combination error (Outdoor unit)
E: 32. Indoor unit main PCB error (Indoor
unit)
E: 35. MANUAL AUTO button error (Indoor
unit)
E: 41. Room temperature sensor error
(Indoor unit)
E: 42. Indoor unit heat exchanger sensor
error (Indoor unit)
E: 51. Indoor unit fan motor error (Indoor
unit)
E: 62. Outdoor unit main PCB error
(Outdoor unit)
E: 64. PFC circuit error (Outdoor unit)
E: 65. IPM error (Outdoor unit)
E: 71. Discharge thermistor error (Outdoor
unit)
E: 73. Outdoor unit heat exchanger
thermistor error (Outdoor unit)
E: 74. Outdoor temperature thermistor error
(Outdoor unit)
E: 84. Current sensor error (Outdoor unit)
E: 94. Trip detection (Outdoor unit)
E: 95. Compressor motor control error
(Outdoor unit)
E: 97. Outdoor unit fan motor error
(Outdoor unit)
E: 99. 4-way valve error (Outdoor unit)
E: A1. Discharge temperature error
(Outdoor unit)
1-1. Error code table (Indoor unit and wired remote controller)
Indoor unit display
Operation [ ]
Timer [ ]
(Green)
(Orange)
1 times
1 times
1 times
1 times
1 times
2 times
1 times
8 times
2 times
2 times
2 times
3 times
3 times
2 times
3 times
5 times
4 times
1 times
4 times
2 times
5 times
1 times
6 times
2 times
6 times
4 times
6 times
5 times
7 times
1 times
7 times
3 times
7 times
4 times
8 times
4 times
9 times
4 times
9 times
5 times
9 times
7 times
9 times
9 times
10 times
1 times
- (03-1) -
Wired
remote
Economy [ ]
controller
(Green)
display
Continuous
11
Continuous
11
Continuous
12
Continuous
18
Continuous
22
Continuous
23
Continuous
32
Continuous
35
Continuous
41
Continuous
42
Continuous
51
Continuous
62
Continuous
64
Continuous
65
Continuous
71
Continuous
73
Continuous
74
Continuous
84
Continuous
94
Continuous
95
Continuous
97
Continuous
99
Continuous
A1
1. Error code