02: Frequency Converter enable/disable
Interface
03: Output frequency setting
Interface
04: ECO enable/disable
Interface
05: ECO voltage range setting
Interface
06: Bypass enable/disable when UPS is off
Interface
240: presents output voltage is 240Vac
Setting
Parameter 2: Enable or disable converter mode.
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
Setting
Parameter 2: Output frequency setting.
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, choose from these frequencies:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
Setting
Parameter 2: Enable or disable ECO function.
ENA: ECO mode enable
DIS: ECO mode disable (Default)
Setting
Parameter 2: Set the acceptable high voltage point and low
voltage point for ECO mode by pressing Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
(Default: +12V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage.
(Default: -12V)