andrews MAXXflo EVO Lite Assembling Instruction Manual page 17

High efficiency condensing stainless steel storage water heater
Hide thumbs Also See for MAXXflo EVO Lite:
Table of Contents

Advertisement

Error
Error Code
Code
Description
110
SLT Lockout
111
Shutdown limit
thermostat
125
Maximum boiler
temperature
exceeded
126
DHW charging
temperature not
reached
127
DHW legionella
temperature not
reached
User operation
3.8.1 Error codes (continued)
Diag.
Notes
Code
306 431
Electronic temperature limits exceeded. General overheating issue. Check for
432 433
pump operation, trapped air and heat exchanger blockages. Monitor tempera-
434 435
tures of system to establish problem area.
436 756
429 818
Safe reset of the error sub code 433 (see above) has not been met. Allow the
water heater to cool further before resetting.
305 412
Mechanical overheat protection circuit is open circuit (connection X18 on
550 551
control PCB). Check connector is fully inserted
754
426 437
Flow temperature heat up gradient exceeded. Check pump operation and
815
presence of trapped air in the heat exchanger. Flow through heat exchanger
may be restricted.
438
Maximum Delta T of system exceeded. Check pump operation and presence
817
of trapped air in the heat exchanger. Flow through heat exchanger may be
restricted.
428
Maximum Delta T of system exceeded. Initial starting of the pump before the
burner is operated, can cause this error. If accompanied by code 429 within
the same minute, this error can be disregarded.
429
Safe reset of the error sub code 428 /438 (see above). Allow the water heater
to cool further before resetting.
427 816
Safe reset criteria has not been met. Allow the water heater to cool further
before resetting.
420 421
Return temperature greater than fl ow temperature. Check that the fl ow and
819 820
return sensors are operating correctly
419 430
Flow temperature limit exceeded. Check for overheating issues and fl ow sen-
813 814
sor (B2) performance.
809 810
Flow temperature not plausible - Reading less than 0
422 423
124
O
C . Check fl ow sensor (B2) and replace if necessary.
425
Return temperature limit exceeded. Check for overheating issues and return
812
sensor (B7) performance.
424
Return temperature not plausible - Reading less than 0
811
124
C . Check return sensor (B7) and replace if necessary.
O
264
Heat exchanger temperatures have been exceeded. Investigate fl ow rates
and controls to determine causes of temporary fault code.
286 500
Temperature supervision lockout. Check pump, shutoff valves, burner and
740
fl ow rates before resetting
501
Temperature has not increased at fl ow sensor after burner start. Check fl ow
sensor is correctly clipped to pipe work.
502
Temperature has not increased at return sensor after burner start. Check
return sensor is correctly clipped to pipe work.
72
Charging temperature not achieved within parameterised time scale. Check
operation and heat up times for heater
73
Check operation of legionella function and DHW system. Legionella setpoint
has not been achieved within 48 hours of the legionella function operating.
When using a secondary return system and sensor, do not set the legionella
function setpoint too high, as the heat losses of the hot water pipework may
not permit this setpoint to be achieved at the return point before the heater.
17
C or greater than
O
O
C or greater than
MAXXfl o EVO Lite