SOL08 / P08
Heat amount capture
3062438_0309
Parameter description
Cylinder assignment example:
BM 0
Wolf
boiler
Cylinder
at the
cylinder 1
BM0
Note: MM = mixer module
In this example, solar cylinder 1 is assigned to the programming
module with address 1 (BM1, and solar cylinder 2 to the
programming module with address 2 (BM2). This requires the
following setting:
SOL07 / P07 = 1
SOL17 / P17 = 2
The setting can be made via the BM with address 0 (BM0) or via
the BM-Solar.
Then the solar module can also be operated from the assigned
programming modules.
System configurations 1, 3, 4, 5, 6 enable the capture of the amount
of heat yielded by the solar thermal system (solar yield).
For this, parameter 08 enables the choice whether yield is
determined by means of the actual or a specified flow rate:
SOL08 / P08 = 0: Heat amount capture disabled
SOL08 / P08 = 1: Yield capture with actual flow rate
SOL08 / P08 = 2: Yield determination with a specified flow rate
Option
BM 1
BM-Solar
MM 1
SM2
Solar
at the
BM1
BM 2
MM 2
Solar
cylinder 2
at BM 2
31