Gas Train; Gas Train Electricity Supply; Gas Feeding Line - Riello Gulliver BS3/M TXL Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

3.4 GAS TRAIN,

(as EN 676)
The gas train is supplied separately, for its adjustment see the enclosed instructions.
GAS TRAIN
TYPE
MBDLE 407 B01
3970548
MBDLE 410 B01
3970549
MBDLE 412 B01
3970550
3.5

GAS TRAIN ELECTRICITY SUPPLY

The gas train's power cables can be fed to the right or
left of the burner, as illustrated in figure 6.
Depending on the entry point, the cable clamp with
pressure test point (1) and simple cable clamp (2) may
need swapping over.
Consequently, you must make sure:
the cable clamp (1) is positioned correctly;
the tube is positioned correctly so that there are no
restrictions likely to impede air flowing to the pres-
sure switch.
WARNING
If necessary, cut the tube to the right size.

3.6 GAS FEEDING LINE

1
– Gas supply pipe
2
– Manual cock (charged to the installer)
3
– Gas pressure gauge (charged to the installer)
4
– Filter
5
– Gas pressure switch
6
– Safety valve
7
– Pressure governor
8
– Adjusting valve
M1 – Gas-supply pressure test point
M2 – Pressure coupling test point
20050873
MATCHED
BURNER
CODE
BS3 - BS4
BS3/M
BS3/M
1
CONNECTIONS
INLET
OUTLET
Rp 3 / 4
Flange 3
Rp 1 1 / 4
Flange 3
Rp 1 1 / 4
Flange 3
1
2
2
3
M1
4
5
D5209
7
GB
USE
Natural gas  150kW and LPG
Natural gas and LPG
Natural gas
D7113
6
7
8
Fig. 6
2
1
Fig. 7
M2

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

20050820

Table of Contents