Parameter
1 Network address
2 Delay for the Mains
Failed event
3 Delay for the Mains
Restored event
4 Battery life counter
5 Interval for repeating
a Service Required mes-
sage
6 6 Adjustment of mains
power voltmeter
7 7 Disablement of
Battery Test Error mes-
sages
8 8 Disablement of
No Battery indication
* If "0" is set for this parameter, the message is issued one time only.
Parameter
Relay control program run-
1 Control
ning right after powering on
Program
the ShPS-12 (or reboot)
Time for the relay to be
2 Relay Activa-
turned on / off for the com-
tion Time
mands Turn On for a Time
and Turn Off for a Time
Selection of monitored pa-
3 Relay Control
rameters to activate the relay
Option
control program

2.2.6 Usage

2.2.6.1. Please refer to 1.4.2 for description of ShPS-12 operation. To be admitted to work with the
equipment, the personnel are obliged to have studied this manual and to have a certificate of
verification of knowledge of accident prevention regulations.
2.2.6.2. Turning the ShPS-12 On
IMPORTANT! Prior to turning on ensure that the ShPS-12 is mounted properly and in
compliance with the connection diagram (refer to Appendix A).
WARNING! To provide the specifications stated, the ShPS-12 box shall be operated with
connected batteries in good conditions. If the batteries are connected but the ShPS-12 issues
Battery Test Error, the batteries shall be requested. The batteries of type specified in 1.2.3 shall
be replaced also at the end of the battery service life stated by their manufacturer. The ShPS-12
supports a battery life counter (see Table 5). Life time set for the counter by a user shall not be
more than that specified by the battery manufacturer.
16
Description
Device address in the RS-485 network
Delay time before transmitting the Mains
Fault event via the RS-485 interface
Delay time before transmitting the Mains
Restored event via the RS-485 interface
Time set for the battery lifetime counter.
When this time expires, the ShPS-12 is-
sues Service Required messages
Interval time for reissuing Service Re-
quired messages resulted due to expired
battery lifetime as set in the counter
Increase or decrease voltage values in
respect to mains voltmeter measurements
Disables the Battery Error messages for
the BAT1 battery
Disables the Battery Error message for
the battery BAT2
Disables indication of missed BAT1
Disables indication of missed BAT2
Programmable Parameters for the Solid State Relay:
Description
4...255 s
4...255 s
1...15 years
1...255 h *
Value
Turn On
Turn Off
Turn On for a Time
Turn Off for a Time
0... 8191.875 s
1. All parameters but for communi-
cations
2. Communications fault
3. Output current overload
4. MIP failure (charger, Uout)
5. Battery failure (missing)
6. Mains voltage is lower than
150V or higher than 250V
7. Enclosure tampering
Range
Factory Value
1...127
127
4 s
4 s
10 years
255 h
± 20 V
0 V
On / Off
Events Enabled
On / Off
On / Off
Indication Enabled
On / Off
Factory Value
Turn Off
8191.875 s
All parameters
but for commu-
nications
Table 5