as specified in 1.2.17. The batteries shall be fully charged before the test (indicated by steady light of
the BATTERY LED).

2.2.5 Programming the ShPS-12

2.2.5.1. Change the network address of the ShPS-12 box. The new address shall be unique and
different from all the addresses of devices connected to the same RS-485 line where this ShPS-12 is
connected (default address is 127).
2.2.5.2. If needed, change the rest configuration parameters according to your intended use of the
ShPS-12 (see Table 5).
To change the ShPS-12 configuration parameters, please use an IBM-compatible computer with the
UProg application installed. To connect the ShPS-12 to a PC COM port, an interface converter shall
be used such as RS-232/RS-485 PI-GR, S2000-PI, or S2000M panel set as interface converter.
Appendix H shows the application window.
The UProg utility can be downloaded at http://bolid.ru.
2.2.5.3. The ShPS-12 door being open, the tamper switch can be used to:
− Mute the buzzer by three short and one long tamper button presses (● ● ● ▬);
Note: Holding button down for 1.5 to 3 sec is long pressing (▬). Holding the button down for 0.1 to
0.5 sec is short pressing (●). Pauses between presses shall not be shorter than 0.1 sec but no longer
than 1sec.
− Reset network address (to set default address 127): ( ▬ ▬ ▬ ●);
− Reset battery life counter and measured capacity (when battery replaced): (● ● ● ▬ ▬).
2.2.5.4. If the network controller is powered from another power supply, the circuits "0 V" of the
ShPS-12 / ShPS-12 mod.01 / ShPS-12 mod.02 box and network controller shall be connected as a
single circuit.
2.2.5.5. The programmable parameters are described in Table 5 and Table 6 (see Appendix H). The
parameters are stored in the nonvolatile memory.
2.2.5.6. Unless the ShPS-12 / ShPS-12 mod.01 / ShPS-12 mod.02 box is the first or the last device
in the RS-485 interface bus then open the XP1 jumper located on the BK-12 board close to the ХТ1
terminal block (which is intended for connecting the devices) – see Appendix A.
2.2.5.7. If the ShPS-12 mod.10 / ShPS-12 mod.11 / ShPS-12 mod.12 box is the first or the last
device in the RS-485 interface bus then loosen the side limiter for connecting the end-of-line resistors
and remove the cover from the BK-12 enclosure. On the BK-12 board, near the terminal block for
connecting the separate RS-485 interface No.2 please find mail-type connectors ХР10 and ХР11.
Closing the connector ХР10 with the jumper provided connects the end-of-line resistor to the separate
RS-485 interface line No.1. Closing the connector ХР11 with the jumper provided connects the end-of-
line resistor to the separate RS-485 interface line No.2.