Connection Scheme - Seco TANARO Series Product Manual

Table of Contents

Advertisement

5.1

Connection Scheme

Notice
An incorrectly dimensioned power supply can destroy the HMI device.
Use a DC power supply with adequate amperage; see Chapter 4. Technical Data
Notice
Safe electrical isolation
For the DC supply, use only power supply units with safe electrical isolation in accordance with IEC 60364-4-41 or HD
384.04.41 (VDE 0100, Part 410), e.g. conforming to the SELV/PELV standard.
The supply voltage must be within the specified voltage range. Otherwise, malfunctions at the HMI device cannot be
ruled out.
Applies to non-isolated system configurations:
Connect the GND connection from the DC power supply output to equipotential bonding for uniform reference potenti-
al. You should always select a central point of termination.
Notice
We recommend using cables with the following specifications
Function
DC supply
Audio
Ethernet
RS485
RS232
CAN
USB
Cable specification
No special requirements
No special requirements; length < 3m
Shielded, type CAT5e SFTP
Shielded data cable, length <30m
Shielded data cable, length <30m
Shielded data cable, length <30m
Shielded USB cable; labeled as "Certified HI-SPEED USB
2.0"; length <3m
PRODUCT MANUAL
TANARO
1 6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tanaro 7.0 of pct ips900-4556r

Table of Contents