Trane GEHB018 Installation page 2

Crankcase heater wiring

Advertisement

2
© 2006 American Standard Inc. All rights reserved
Installation
Literature change history
PART-SVN100A-EN (October 2006) manual first release.
Warnings and Cautions
NOTICE: Warnings and Cautions appear at appropriate sections
throughout this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
CAUTION: Indicates a situation that may result in equipment or prop-
erty-damage only accidents.
Instructions
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all
motor start/run capacitors before servicing. Follow proper lockout/tagout
procedures to ensure the power cannot be inadvertently energized. Verify
with an appropriate voltmeter that all capacitors have discharged. Failure to
disconnect power and discharge capacitors before servicing could result in
death or serious injury.
Note: For additional information regarding the safe discharge of capacitors,
see PROD-SVB06A-EN or PROD-SVB06A-FR.
This KIT includes a relay, wiring assembly, and crankcase (sump) heater. The
following information and wiring digram shown in Figure 1 (p. 3) should be
used to install this device.
HTR06811 - Crankcase heater, 30 Watt, 5.07" diameter, 208/230 Vac or
HTR06851 - Crankcase heater, 30 Watt, 5.07" diameter, 265 Vac
and
RLY01357 - DPDT relay, 24 Vac coil 50/60 HZ, 3 A 277 Vac pilot duty contacts
WIR004682 - Wire harness for adding crankcase heater
1 Turn off all power sources to the unit. Follow proper lock out and tag out
procedures.
2 Install mechanical components, heater and relay.