Four-Inch (101.6 Mm) Ruptureguard; Installation - Trane RuptureGuard CDHF Installation, Operation And Maintenance Manual

Pressure relief system option
Table of Contents

Advertisement

I I n n s s t t a a l l l l a a t t i i o o n n
Figure 15. Three-inch (76.2 mm) RuptureGuard mounting
Chiller
Gasket
N N o o t t e e s s : :
Where space permits, the 3-in. (76.2 mm) RuptureGuard ™ can be bolted directly to the chiller flange.
Adaptations may occur in the field-fabricated vent piping system installation due to variations on specific job
sites. It may be necessary to fabricate an elbow, spool adapter, off-set, or other component to accommodate
these variations. Follow all instructions in this manual and contact your local Trane representative with any
questions.
Figure 16. Three-inch (76.2 mm) RuptureGuard
flange, in. (mm)
16
Acceptable
Locally
Gasket
Provided Piping
Options
Ø 0.750 (Ø 19.050), 8X
Ø 6.000 (Ø 152.400) B.C.
BOTH FLANGES
TM
RuptureGuard
Gasket
Flow Direction
Note: All piping per
ASHRAE Standard 15.
Four-inch (101.6 mm)
RuptureGuard Installation
R R e e f f r r i i g g e e r r a a n n t t M M a a y y B B e e U U n n d d e e r r P P o o s s i i t t i i v v e e
P P r r e e s s s s u u r r e e ! !
F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w i i n n s s t t r r u u c c t t i i o o n n s s b b e e l l o o w w c c o o u u l l d d r r e e s s u u l l t t i i n n
a a n n e e x x p p l l o o s s i i o o n n w w h h i i c c h h c c o o u u l l d d r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r
s s e e r r i i o o u u s s i i n n j j u u r r y y o o r r e e q q u u i i p p m m e e n n t t d d a a m m a a g g e e . .
S S y y s s t t e e m m c c o o n n t t a a i i n n s s r r e e f f r r i i g g e e r r a a n n t t a a n n d d m m a a y y b b e e u u n n d d e e r r
p p o o s s i i t t i i v v e e p p r r e e s s s s u u r r e e ; ; s s y y s s t t e e m m m m a a y y a a l l s s o o c c o o n n t t a a i i n n o o i i l l . .
R R e e c c o o v v e e r r r r e e f f r r i i g g e e r r a a n n t t t t o o r r e e l l i i e e v v e e p p r r e e s s s s u u r r e e b b e e f f o o r r e e
o o p p e e n n i i n n g g t t h h e e s s y y s s t t e e m m . . S S e e e e u u n n i i t t n n a a m m e e p p l l a a t t e e f f o o r r
r r e e f f r r i i g g e e r r a a n n t t t t y y p p e e . . D D o o n n o o t t u u s s e e n n o o n n - - a a p p p p r r o o v v e e d d
r r e e f f r r i i g g e e r r a a n n t t s s , , r r e e f f r r i i g g e e r r a a n n t t s s u u b b s s t t i i t t u u t t e e s s , , o o r r n n o o n n - -
a a p p p p r r o o v v e e d d r r e e f f r r i i g g e e r r a a n n t t a a d d d d i i t t i i v v e e s s . .
Locally
Provided Piping
to Vent and
Drip Leg
W W A A R R N N I I N N G G
CTV-SVX06J-EN