Grounding Afdh Cabinet - Trane AFDH Installation Instructions Manual

D-frame upgrade adaptive frequency drive for tracer adaptiview centrifugal chiller
Table of Contents

Advertisement

Installation
Note: In some cases, the top plate with conduit hubs
from the original starter may be reused and
installed over the incoming wire access cut-out
on the top of the cabinet, in place of the two-
piece access covers.
a. Install the appropriate conduit hubs before
reinstalling the access door pieces on top of the
cabinet.
3. Route the input wire leads into the cabinet and connect
them to circuit breaker terminals L1, L2, and L3.
a. The torque specification for these terminal
connections is 31 ft·lb.
Figure 31. Factory installed input disconnect circuit
breaker
1.
Input disconnect circuit breaker
2.
Nameplate.
3.
Input power terminals. Terminal connections should be torqued to
31 ft·lb.
Remote Mount
Shorting buss bars are not required for remote mount
units. Terminals are interconnected at the remote mount
panel.
48

Grounding AFDH Cabinet

WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
NOTICE:
Use Copper Conductors Only!
Failure to use copper conductors could result in
equipment damage as unit terminals are not designed
or qualified to accept other types of conductors.
1. Run a suitable, unbroken, grounding conductor from
the drive cabinet's ground connection terminal to the
motor's ground terminal, and then on to earth ground.
Figure 32. Location of AFDH cabinet ground terminal
1.
Cabinet ground connection terminal
1
AFDH-SVN005B-EN