previously. Key in the value and press ENTER key. The
new value will be entered into memory and the display will
advance to the next programmable value.
"DEFAULT" VALUE PROGRAMMING IN THE
PROGRAM MODE
Programmable values may be individually programmed
at start-up or anytime thereafter. For ease of
programming, once the type of refrigerant is programmed
in under the PROGRAM key, a password may be
programmed in to automatically program default values
into the micro. This will preset all programmable values
under the PROGRAM key to values that will allow
operation of the chiller under most operating conditions.
This allows quick start-up programming for typical chilled
water applications.
To program the default values into the micro after the
refrigerant type has been programmed, press the
PROGRAM key, key in the numbers "6140", and press
ENTER. As the numbers are keyed in, Qs will appear:
When the ENTER key is pressed, the following message
will appear:
P R O G R A M
M O D E
Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q
TABLE 4 – PROGRAM MODE DEFAULT VALUES
PROGRAMMABLE OPTION
REFRIGERANT TYPE
DISCHARGE PRESSURE CUTOUT (R-22)
DISCHARGE PRESSURE CUTOUT (R-134a)
LOW AMBIENT TEMP CUTOUT
HIGH AMBIENT TEMP CUTOUT
DISCHARGE PRESSURE UNLOAD (R-22)
DISCHARGE PRESSURE UNLOAD (R-134a)
AVERAGE CURRENT UNLOAD
ANTI RECYCLE TIME
LEAVING CHILLED LIQUID TEMP CUTOUT
SUCTION PRESSURE CUTOUT (R-22)
SUCTION PRESSURE CUTOUT (R-134a)
LAG COMPRESSOR START POINT
LAG COMPRESSOR DIFFERENTIAL OFF
FAN CONTROL DISCHARGE PRESSURE SET POINT (R-22)
FAN CONTROL DISCHARGE PRESSURE SET POINT (R-134a)
FAN ON/OFF DIFFERENTIAL
SYSTEM 1 MOTOR CURRENT FLA
SYSTEM 2 MOTOR CURRENT FLA
LIQUID INJECTION TEMP LIMIT
SYSTEM 1 FULL LOAD CONDENSER TEMPERATURE
SYSTEM 2 FULL LOAD CONDENSER TEMPERATURE
COMMUNICATIONS MODE
LOAD SHARING MODE
ECONOMIZER VALVE ON POINT
ECONOMIZER VALVE OFF POINT
96
D E F A U L T
S E T P O I N T S ?
1
=
Y E S ,
Key in a "1" for YES, if default setpoints in Table 4 are
desired. Key in a "0" for NO, if individually programmed
values are desired. After the desired option is
programmed, press ENTER to store the selection into
memory.
NOTE: Keep in mind that it is often easier to select
Default Setpoints and then reprogram a few that
require changing, versus programming each
individual program option.
If a "0" is selected, the display will return to the STATUS
display. If a "1" is selected, the display will momentarily
display the message shown below before returning to the
STATUS display.
P R O G R A M
O P T I O N S
T O
D E F A U L T
A list of the default values entered into memory, if this
program option is selected, is shown in Table 4.
PROGRAM 6140 DEFAULT
0°F (LOW AMBIENT)
25°F (STANDARD AMBIENT)
36°F (BRINE)
36°F (WATER)
44 PSIG (BRINE)
44 PSIG (WATER)
19 PSIG (BRINE)
19 PSIG (WATER)
0
=
N O ,
1
S E T
V A L U E S
N/A
399 PSIG
275 PSIG
130°F
375 PSIG
255 PSIG
105%
600 SEC.
70%
50%
230 PSIG
102 PSIG
50 PSIG
N/A
N/A
180°F
N/A
N/A
N/A
2
50%
40%