York Millennium YCAS 316 Installation Operation & Maintenance page 115

Air cooled screw liquid chillers air cooled screw hermetic
Table of Contents

Advertisement

YORK INTERNATIONAL CORPORATION
MILLENNIUM SCREW CHILLER
ISN OPTION ENABLED
SOFTWARE VERSION W.04F.02.500.02
SYSTEM STATUS
11:43PM 01 JAN 96
SYS 1 COMPRESSOR RUNNING
SYS 2 COMPRESSOR RUNNING
RETURN WATER TEMP
LEAVING WATER TEMP
LOW WATER CUTOUT
COOLING RANGE
TARGET TEMP
AMBIENT AIR TEMP
LOW AMBIENT CUTOUT
LOW PRESSURE CUTOUT
LEAD SYSTEM
LOCAL REMOTE SETTING:
SYSTEM 1 DATA
COMPRESSOR STATUS
RUN TIME
AVERAGE MTR
PHASE L1 MTR
PHASE L2 MTR
PHASE L3 MTR
DIFF OIL PRESSURE
SUCTION PRESSURE
SATURATED SUCTION
SUCTION TEMP
SUPERHEAT
DISCHARGE PRESSURE
SATURATED DISCHARGE
DISCHARGE TEMP
OIL TEMP
LIQUID INJECTION VALVE
FORWARD FANS
REVERSE FANS
LIQUID LINE SOLENOID
RUN PERMISSIVE
SYSTEM 2 DATA
COMPRESSOR STATUS
RUN TIME
AVERAGE MTR
PHASE L1 MTR
PHASE L2 MTR
PHASE L3 MTR
DIFF OIL PRESSURE
SUCTION PRESSURE
SATURATED SUCTION
SUCTION TEMP
SUPERHEAT
DISCHARGE PRESSURE
SATURATED DISCHARGE
DISCHARGE TEMP
OIL TEMP
LIQUID INJECTION VALVE
FORWARD FANS
REVERSE FANS
LIQUID LINE SOLENOID
RUN PERMISSIVE
S M T W T F S
SUN
START=00:00AM
MON START=00:00AM
TUE
START=00:00AM
WED START=00:00AM
THU
START=00:00AM
FRI
START=00:00AM
SAT
START=00:00AM
HOL
START=00:00AM
FIG. 32 – OPER DATA PRINT-OUT
The most recent fault will always be stored as SAFETY
SHUTDOWN NO. 1 (See printout Fig. 33). Identically for-
matted fault information will then be printed for SAFETY
SHUTDOWN NO. 2 and SAFETY SHUTDOWN NO. 3.
YORK INTERNATIONAL
49.1 DEGF
49.3 DEGF
36.0 DEGF
42.0 TO 44.0 DEGF
43.0 DEGF
70.2 DEGF
25.0 DEGF
44 PSIG
SYS 1
LOCAL
OFF
0- 0-31-26 D-H-M-S
65 %FLA
66 %FLA
65 %FLA
65 %FLA
9 PSID
72 PSIG
42.6 DEGF
49.0 DEGF
6.4 DEGF
214 PSIG
106.2 DEGF
128.1 DEGF
131.2 DEGF
OFF
OFF
OFF
ON
ON
ON
0- 0-26-11 D-H-M-S
65 %FLA
65 %FLA
65 %FLA
65 %FLA
4 PSID
62 PSIG
35.8 DEGF
47.2 DEGF
11.4 DEGF
215 PSIG
106.4 DEGF
134.8 DEGF
85.2 DEGF
OFF
OFF
OFF
ON
ON
Q=HOLIDAY
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
Information contained in the SAFETY SHUTDOWN Buff-
ers is very important when attempting to troubleshoot a
system problem. This data reflects the system condi-
tions at the instant the fault occurred and often reveals
other system conditions which actually caused the safety
threshold to be exceeded. See Fig. 33 for a sample of
the History Buffer Printout.
LOCAL DISPLAY READOUT
Oper Data
The OPER DATA key also allows the user to scroll through
additional real time display information about the chiller
system which is not available from the "DISPLAY" keys.
This information covers a wide range of data which in-
cludes fan status, loading status, liquid line solenoid sta-
tus, run time, etc. A total of 15 different displays are
offered.
When the OPER DATA key is pressed, the following
message will appear:
P R E S S
E N T E R
D I S P L A Y
D A T A
Repetitively pressing the ENTER key allows the opera-
tor to scroll through the 15 available displays.
In the information that follows, a sample message along
with an explanation of its meaning is provided for all 15
messages.
L O A D
T I M E R
U N L O A D
T I M E R
The top message provides a real time display of the time
left on the Load Timer. The Load Timer is a constantly
recycling timer that the micro utilizes in conjunction with
"rate control" and "temperature deviation from setpoint"
to determine when loading should occur.
NOTE: This counter may appear to not count according
to actual time. This is a result of the micro's al-
gorithm compensating for changing loading re-
quirements.
The bottom message provides a real time display of the
time left on the Unload Timer. The Unload Timer is a con-
stantly recycling timer that the micro utilizes in conjunc-
tion with "rate control" and "temperature deviation from
setpoint" to determine when unloading should occur.
NOTE: This timer may appear to not count according to
actual time. This is a result of the micro's algo-
rithm compensating for changing unloading re-
quirements.
FORM 201.10-NM1
OPER
DATA
T O
7 0
S E C
6 0
S E C
115