Electrical Data - York Millennium YCAS 316 Installation Operation & Maintenance

Air cooled screw liquid chillers air cooled screw hermetic
Table of Contents

Advertisement

(Each Power Supply Individually Protected with Field Supplied Branch Circuit Protection)
STYLE
MODEL
VOLTS
MIN NF
MCA
1
60 Hz
DISC SW
200
374
230
337
YCAS140
380
204
460
165
575
136
200
447
230
404
YCAS160
380
244
460
197
575
161
200
509
230
458
YCAS170
380
279
460
224
575
183
200
509
230
458
YCAS180
380
279
460
224
575
183
200
570
230
508
YCAS190
380
311
460
250
575
203
380
392
YCAS216
460
314
575
253
380
337
YCAS216X
460
272
575
224
380
392
YCAS236
460
314
575
253
380
397
YCAS236X
460
319
575
260
380
414
YCAS246
460
332
575
267
460
324
YCAS266X
575
263
NOTES for Electrical Data, pages 18 - 25:
1.
Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all
other loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the
system #1 MCA values in the YCAS Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.
2.
The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440-12A1.
3.
Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLA's (U.L. Standard 1995, Section 36.1).
4.
Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,
per N.E.C. 440-22.
5.
Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2.
6.
Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per
U.L. 1995 Fig. 36.2.
7.
The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2) or (3)
indicated the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must be
determined based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based on the
National Electric Code and using copper connectors only. Field wiring must also comply with local codes.
8.
A ground lug is provided for each compr. system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.
9.
The supplied disconnect is a "Disconnecting Means" as defined in N.E.C. 100.B, and is intended for isolating the unit from the available
power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
18
STANDARD DUAL POWER SUPPLY
SYSTEM #1 FIELD SUPPLIED WIRING
D.E. FU
C.B.
2
3
4
5
MIN.
MAX.
MIN.
400
450
600
450
400
400
500
400
200
250
300
250
200
200
250
200
200
175
225
175
600
600
700
600
400
500
600
500
400
300
400
300
200
250
300
250
200
200
250
200
600
700
800
700
600
600
700
600
400
350
450
350
400
300
350
300
200
225
300
225
600
700
800
700
600
600
700
600
400
350
450
350
400
300
350
300
200
225
300
225
600
700
800
700
600
600
800
600
400
400
500
400
400
300
400
300
200
225
300
250
400
500
600
500
400
400
500
400
400
300
400
300
400
400
500
400
400
350
450
350
400
300
350
300
400
500
600
500
400
400
500
400
400
300
400
300
400
500
600
500
400
400
500
400
400
350
400
350
400
500
700
500
400
400
500
400
400
350
450
350
400
400
500
400
400
350
400
350
(LUGS) WIRE RANGE
6
7
MAX.
WYE-DELTA
ACR-LINE
600
(2) #6-250
N/A
500
(2) #6-250
N/A
300
(2) #6-250
N/A
250
(2) #8-1/0
(1) #6-250
200
(2) #8-1/0
(1) #6-250
700
(2) 1/0-500
N/A
600
(2) #6-250
N/A
400
(2) #6-250
N/A
300
(2) #6-250
(1) #6-250
250
(2) #8-1/0
(1) #6-250
800
(2)1/0-500
N/A
700
(2)1/0-500
N/A
450
(2) #6-250
N/A
350
(2) #6-250
(1) 1/0-500
250
(2) #8-1/0
(1) #6-250
800
(2) 1/0-500
N/A
700
(2) 1/0-500
N/A
450
(2) #6-250
N/A
350
(2) #6-250
(1) 1/0-500
250
(2)#8-1/0
(1) #6-250
800
(2) 1/0-500
N/A
800
(2) 1/0-500
N/A
500
(2) #6-250
N/A
400
(2) #6-250
(1) 1/0-500
300
(2) #6-250
(1) 1/0-500
600
(2) #6-250
N/A
500
(2) #6-250
(1) 1/0-500
400
(2) #6-250
(1) 1/0-500
500
(2) #6-250
N/A
450
(2) #6-250
(1) 1/0-500
300
(2) #6-250
(1) #6-250
600
(2) #6-250
N/A
500
(2) #6-250
(1) 1/0-500
400
(2) #6-250
(1) 1/0-500
600
(2) #6-250
N/A
500
(2) #6-250
(1) 1/0-500
400
(2) #6-250
(1) 1/0-500
700
(2) 1/0-500
N/A
500
(2) #6-250
(1) 1/0-500
400
(2) #6-250
(1) 1/0-500
500
(2) #6-250
(1) 1/0-500
400
(2) #6-250
(1) 1/0-500
COMPRESSOR
FANS
7
RLA
Y LRA X LRA
FLA (EA)
267
424
1358
10.0
231
362
1159
12.0
146
216
691
5.2
116
181
579
5.0
92
145
463
4.9
325
492
1575
10.0
284
462
1479
12.0
178
261
835
5.2
141
217
695
5.0
113
170
543
4.9
375
587
1879
10.0
328
538
1723
12.0
206
316
1013
5.2
163
262
838
5.0
130
204
655
4.9
375
587
1879
10.0
328
538
1723
12.0
206
316
1013
5.2
163
262
838
5.0
130
204
655
4.9
424
785
2492
10.0
367
641
2035
12.0
232
401
1272
5.2
183
331
1051
5.0
147
270
857
4.9
296
483
1531
5.2
235
398
1261
5.0
187
311
987
4.9
244
316
1013
5.2
193
262
838
5.0
155
204
655
4.9
296
483
1531
5.2
235
398
1261
5.0
187
311
987
4.9
292
401
1272
5.2
231
331
1051
5.0
184
270
857
4.9
314
483
1531
5.2
249
398
1261
5.0
198
311
987
4.9
235
398
1261
5.0
187
311
987
4.9