Input
Model name
power
(W)
LGH-F300RVX2-E
235
LGH-F380RVX2-E
340
LGH-F470RVX2-E
425
LGH-F600RVX2-E
515
LGH-F940RVX2-E
850
LGH-F1200RVX2-E
1030
* The above values apply during energy recovery ventilation when the fan speed is set to Fan speed 4 at the rating
pressure loss and 230 V / 60 Hz.
* For the specifications at the other frequency or voltages, see the spec. sheets.
* The values given in the table for the noise level reflect the levels measured at a position 4.9 feet (1.5 m) immedi-
ately below the unit in an anechoic chamber.
* Noise change or increase may occur because of the Bypass-Automatic function or Automatic fan speed change
by timer setting and/or other functions.
* Temperature Exchange efficiency (%) are average of summer and winter condition.
* Mitsubishi Electric measures products according to ISO 16494:2014, therefore characteristic values are mea-
sured by chamber method.
* On-site commissioning measurements by pitot tube method could be as much 20% different from ISO test room
conditions. If the measuring point is close to sources of turbulence like bends, contractions and dampers, etc., it is
difficult to measure air volume correctly. A straight duct length more than 10 D (D=duct diameter) from the source
of turbulence is recommended for correct measurement. On-site measurement should therefore be measured
in accordance with BSRIA guideline (Commissioning Air System. Application procedures for buildings AG3/89.3
(2001)).
Remote controller
Model name
Power supply requirement
Power consumption
Transmission cable
Total wiring length
Number of controllable Lossnay units
Environmental condition
Size
Weight
Specific
Air volume
Fan
power
(CFM) (CMH) (W/CFM) (InH
300
510
0.78
380
646
0.89
470
799
0.91
600
1019
0.86
940
1597
0.91
1200
2039
0.86
Non polarized 2-core cable (AWG 22 (0.3 mm
15 Lossnay units maximum (Max. 2 remote controllers installable)
Temperature: 32 to 104ºF (0 to 40°C)
Humidity: 30% to 90% relative humidity (no condensation)
4 22/32 x 4 22/32 x 3/4 inch
(120 x 120 x 19 mm)
Static
Exchange efficiency (%)
pressure
Tempe-
O) (Pa)
2
rature
Heating Cooling
1.00
250
65.5
63.0
0.86
215
65.0
61.0
1.00
250
69.0
64.0
0.86
215
67.0
64.0
1.00
250
69.0
64.0
0.86
215
67.0
64.0
PZ-62DR-EA
12 V DC (Supplied from Lossnay unit)
219 yd. (200 m) maximum
9/16 lbs (0.25 kg)
─ 5 ─
Dia. of the
Noise
centrifugal
(dB)
Enthalpy
(Inch (mm))
50.0
37.0
8 3/4 (220)
49.0
38.0
9 5/8 (245)
51.0
40.0
9 5/8 (245) 110
50.0
41.0
9 5/8 (245) 123
51.0
43.0
9 5/8 (245) 225 102
50.0
43.0
9 5/8 (245) 251 114
PZ-43SMF-E
0.3 W
2
) sheathed cable)
4 22/32 x 2 3/4 x 19/32 inch
(120 x 70 x 15 mm)
7/32 lbs (0.10 kg)
Weight
fan
(lbs) (kg)
75
34
90
41
50
56

Hide quick links: