[8] Remove the separator.
[9] Remove the screws (
For LGH-F300RVX2-E
Air supply fan assembly
Assembly precaution
When attaching the centrifugal fan, tighten the special nut to the specified tightening torque.
Tightening torque for the special nut
LGH-F300RVX2-E
LGH-F380RVX2-E
LGH-F470RVX2-E to LGH-F1200RVX2-E
* Remove the Air exhaust fan assembly in the same manner as the steps [7] to [9].
Six PTT screws 5×10, indicated by
), and draw the fan assembly out from the main unit.
For LGH-F380RVX2-E to LGH-F1200RVX2-E
Special nut (M8)
3.43 ± 0.4 N.m
Special nut (M10) 7.30 ± 0.5 N.m
Special nut (M12) 30.87 ± 2.45 N.m
─ 43 ─
Separator
Air supply fan assembly
*The figure shows LGH-F470RVX2-E.