Error
LED1
LED2
Code
(green)
(red)
6831
9
PZ-62DR-EA
blinks
communica-
tion error (no
reception)
6832
9
PZ-62DR-EA
blinks
communica-
tion error (syn-
chronization
recovery error)
6833
9
PZ-62DR-EA
blinks
communica-
tion error
(hardware
error)
6834
9
PZ-62DR-EA
blinks
communica-
tion error (start
bit detection
error)
7113
10
Function set-
blinks
ting error
Symptom
Faulty connection of the
PZ-62DR-EA transmission cable
PZ-62DR-EA is connected to the ter-
minals (TB5 [A] [B]).
Faulty connection of the
PZ-62DR-EA transmission cable
Faulty connection of the
PZ-62DR-EA transmission cable
Faulty connection of the
PZ-62DR-EA transmission cable
The group contains two or more Loss-
nay units with the same address.
The model selection switch (SW6) is
not set correctly.
Improper power circuit board is used.
The applicable circuit boards must
be used as shown below.
LGH-F300 and 380 types:
LG-X08DC-P4
LGH-F470 and 600 types:
LG-X08DC-P6
LGH-F940 and 1200 types:
LG-X08DC-P6 (Lower unit)
LG-X08DC-P5 (Upper unit)
Cause
─ 38 ─
Corrective action
Check the items described in (1) [2].
If the error re-occurs, check for
noise on the transmission cable.
If the above does not correct the
problem, replace the Lossnay con-
trol circuit board or PZ-62DR-EA
remote controller.
Connect PZ-62DR-EA to the termi-
nals (TM4 [1] [2]). (See the Lossnay
Operating/Installation Instructions or
PZ-62DR-E Instruction Book.)
Check the items described in (1) [2].
If the error re-occurs, check for
noise on the transmission cable.
If the above does not correct the
problem, replace the Lossnay con-
trol circuit board or PZ-62DR-EA
remote controller.
Check the items described in (1) [2].
If the error re-occurs, check for
noise on the transmission cable.
If the above does not correct the
problem, replace the Lossnay con-
trol circuit board or PZ-62DR-EA
remote controller.
Check the items described in (1) [2].
If the error re-occurs, check for
noise on the transmission cable.
If the above does not correct the
problem, replace the Lossnay con-
trol circuit board or PZ-62DR-EA
remote controller.
Set unique addresses to these
units.
Make the SW6 setting appropriate
for the model. (See Chapter 8. (8)
Setting status record (page 52).)
Check that the applicable power
circuit board is connected.